Meter Display List - Available Items With Obis Codes - Landis+Gyr E350 Series User Manual

2, 3-phase
Table of Contents

Advertisement

40/56
5.2.9
Meter Display List – Available Items with OBIS Codes
© Landis+Gyr
Index value
Item
(OBIS code)
F.F
Error code (always first in the list)
32.7
VRMS Phase L1 (L12 in ZFFxxx meters)
52.7
VRMS Phase L2 (not for 3-wire ZFFxxx
meters)
72.7
VRMS Phase L3 (L32 in ZFFxxx meters)
31.7
IRMS Phase L1
51.7
IRMS Phase L2 (not for 3-wire ZFFxxx
meters)
71.7
IRMS Phase L3
33.7
Power factor phase L1 (4-wire ZMF1xx
meters only)
53.7
Power factor phase L2 (4-wire ZMF1xx
meters only)
73.7
Power factor phase L3 (4-wire ZMF1xx
meters only)
13.7
Power Factor Phase Summation
14.7
Mains frequency
C.1.0
ID1.1 Meter ID (8 characters)
0.0
Customer identification (16 character
string) (Readout)
0.0.1
ID1.2 Customer ID_1 (characters 1-8)
0.0.2
ID1.3 Customer ID_2 (characters 9-16)
C.1.1
ID1.4 Manufacturing ID (8 characters)
1.8.0
Total active energy import
1.8.X
Active energy import rate X (X = 1...6)
2.8.0
Total active energy export
2.8.X
Active energy export rate X (X = 1...6)
3.8.0
Total reactive energy import
3.8.X
Reactive energy import rate X (X = 1...6)
4.8.0
Total reactive energy export
4.8.X
Reactive energy export rate X (X = 1...6)
0.2.0
Firmware Version
0.2.1
Scheme / Parameter ID
OFF
Blank Display - All segs OFF
ON
All Segments On - All segs ON
FLASH
All Segments Flash - All segs FLASH
D000027979 en t – E350 Series 2, 3-Phase ZxF100Ax/Cx – User Manual
Operation
Meter firmware
version
[M26...]

Hide quick links:

Advertisement

Table of Contents
loading