Installation/Uninstallation

4
Installation/Uninstallation
4.1

Mounting the Meter

D000027979 en t – E350 Series 2, 3-Phase ZxF100Ax/Cx – User Manual
This meter is intended for indoor use only
In cases where an outdoor installation is unavoidable, care must be taken
to ensure the meter is installed within a suitable enclosure to maintain the
operating environment in accordance with the meter specification. Such
enclosures must be securely sealed to avoid the risk of meter damage as a
consequence of exposure to the external environment including (but not
limited to) extreme temperatures, humidity and insect ingress.
The meter should be mounted as follows on the meter board or similar
device provided for this purpose (see also section 3.4 "Dimensions"):
1.
Find the correct position for the meter. Ensure there are no wires
underneath the holes to be drilled.
2.
Define the desired form of fixing (open or covered meter mounting).
3.
Ensure with a phase tester or universal measuring instrument that the
connecting wires are not live.
75 mm
150 mm
Fig. 4.1 Drilling plan
4.
Mark the three fixing points (suspension triangle as shown in the
drilling plan Fig. 4.1) on the mounting surface provided.
5.
Drill the three holes.
6.
Unscrew the meter terminal cover.
7.
For open meter mounting insert the meter suspension eyelet – this is
supplied in the terminal cover – into the corresponding opening at the
rear side of the meter until the suspension eyelet engages (see Fig. 4.2).
25/56
© Landis+Gyr