Landis+Gyr E350 Series User Manual page 32

2, 3-phase
Table of Contents

Advertisement

32/56
Media icons
Disconnect icon
Tamper alert
indicator
Phase voltage
indications
Arrow symbols
Index field
© Landis+Gyr
The media icons represent the medium measured (from left to right water,
gas, heating and electricity). The media icon displayed corresponds to
group A of the OBIS identification code (see also section 5.2.3).
The electricity media icon is either on, if data from the internal meter is
displayed, or flashing, if data from an external meter is displayed
(automatically controlled). The water, gas and heating media icons are also
flashing, if data from an external source is displayed.
This icon indicates that the respective media (represented by the
displayed media icon) is disconnected by the supply control switch.
Icon ON:
Supply control switch open (circuit interrupted)
Icon OFF:
Supply control switch closed (circuit closed, current can
flow)
Icon flashing:
Supply control switch open, can be closed locally (push
button)
This operation is the preset. The operation will be controlled by the installed
module. Please refer to the manual of the module for valid operation mode.
Alternatively to this indication, a display of the supply control switch status
can be in the installed module and the display on the LCD can be disabled.
This icon is switched on when the meter has detected the parameterised
tamper event (either terminal cover, supply control switch or strong
magnetic field).
L
L
L
3
1
2
The phase voltage indications are switched on, if the respective phase
voltages are present. It can be selected by parameterisation whether all the
phase voltage indications are flashing if the rotating field goes in the wrong
direction and/or whether they are flashing if the energy flow is reverse in
the corresponding phase. The meter can also be configured so that it will
flash in service mode only.
The 6 arrow symbols indicate the active rate as marked on the faceplate.
It can be parameterised whether the arrow symbol for the active rate is on
or flashing.
Up to 5-digit indices that define the value in the value field with groups C, D
and E (and partly group B) of the OBIS identification code (see following
section) are displayed in this field.
Examples:
1.8.0 indicates that the status (group D = 8) of total (group E = 0) active
energy import of all phases (group C = 1) is displayed in the value field.
0.9.1 indicates that the local time is displayed in the value field.
D000027979 en t – E350 Series 2, 3-Phase ZxF100Ax/Cx – User Manual
Operation

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents

Save PDF