Ratio monitor / totalizer with high / low alarms and analog outputs, signal input flowmeter: pulse, namur and coil, signal outputs: 4-20ma / 0-10v ref. ratio or flow rate, alarm outputs: up to three flow rate alarm outputs, options: intrinsically safe, mo (64 pages)
Page 1
Signal input flowmeter: (0)4-20mA Signal outputs: 4-20mA, alarm outputs ref. flowrate and pulse ref. total Alarm outputs: maximum four flowrate alarms Options: Intrinsically Safe, Modbus communication, external reset and backlight F-Series - Field mounted indicators for safe and hazardous areas. More info: www.fluidwell.com/fseries.
Intrinsically Safe applications: follow the instructions as mentioned in Chapter 5 and consult “Fluidwell F1..-..-XI - Documentation for Intrinsic Safety”. DISPOSAL At the end of its life this product should be disposed of according to local regulations regarding waste electronic equipment.
Page 4 CONTENTS MANUAL Safety instructions ..........................2 Disposal .............................. 2 Safety rules and precautionary measures ..................2 About the operation manual ....................... 3 Contents manual ..........................3 ............................Introduction ................................6 1.1. System description of the F113-A ................6 ............................
Page 5
Page 5 ......................... Appendix B: Problem solving ................................40 ....................Appendix C: Communication variables ................................40 Appendix D: ....................Declaration of Conformity ................................43 Index of this manual ......................................................... 46 List of figures in this manual ......................46 FW_F113-A_v0601_01_EN...
Page 6 INTRODUCTION 1.1. SYSTEM DESCRIPTION OF THE F113-A Functions and features The flowrate / totalizer model F113-A is a microprocessor driven instrument designed to display flowrate, total and accumulated total as well as the monitoring of the flowrate for high / low values. This product has been designed with a focus on: ...
Page 7 OPERATIONAL 2.1. GENERAL The F113-A may only be operated by personnel who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed. Take careful notice of the " Safety rules, instructions and precautionary measures " in the front of this manual.
Page 8
Page 8 Display flowrate / total or flowrate This is the main display information of the F113-A. After selecting any other information, it will always return to this main display automatically. Total is displayed on the upper-line of the display and flowrate on the bottom line.It is possible to display flowrate only with the large 17mm digits;...
Page 9 CONFIGURATION 3.1. INTRODUCTION This and the following chapters are exclusively meant for electricians and non-operators. In these, an extensive description of all software settings and hardware connections are provided. Mounting, electrical installation, start-up and maintenance of the instrument may only be carried out by trained personnel authorized by the operator of the facility.
Page 10
Page 10 Selection of function-group and function: SETUP is divided into several function groups and functions. Select a setup menu Select a menu item with the CLEAR/ key. with the SELECT/ key. To change or select a value: Momentarily, press the PROG/ENTER key. The program indicator start to flash.
Page 12 3.2.3. EXPLANATION OF SETUP-FUNCTIONS 1 - TOTAL UNIT SETUP 11 determines the measurement unit for total, accumulated total and pulse output. The following units can be selected: L; m3; kg; lb; GAL; USGAL; bbl; no unit Alteration of the measurement unit will have consequences for operator and SETUP-level values.
Page 13 SPAN With the span, the flowmeter signal is converted to a quantity. The span for flowrate is determined on the basis of the selected measurement unit and time unit at 20mA. Enter the span in whole numbers (decimals are set with SETUP 25). The more accurate the span, the more accurate the functioning of the system will be.
Page 14 5 - POWER MANAGEMENT When used with the internal battery option, the user can expect reliable measurement over a long period of time. The F113-A has several smart power management functions to extend the battery life time significantly. Two of these functions can be set: LCD NEW The calculation of the display-information influences the power consumption significantly.
Page 15 CUT-OFF To ignore e.g. leakage of the flow or vibration, a low-flow cut-off can be set as percentage over the full range of 16mA (or 20mA / 10V). When the analog value is less then required with this setting, the signal will be ignored.
Page 16 The analog output value can be programmed “up-side-down” if desired, so 4mA at maximum flowrate for example! CUT-OFF To ignore leakage of the flow for example, a low flow cut-off can be set as a percentage of the full range of 16mA (or 20mA / 10V). When the flow is less than the required rate, the current will be 4mA.
Page 17 RELAY 1 Assign the output function to R1: high alarm, low alarm, high-high alarm, low-low alarm, flowrate alarm or pulse output (max 5Hz). Note: Intrinsically safe applications: this setting has no influence on any output; please read 83: R3. RELAY 2 Assign the output function to R2: high alarm, low alarm, high-high alarm, low-low alarm, flowrate alarm or pulse output (max 60Hz).
Page 18 INSTALLATION 4.1. GENERAL DIRECTIONS Mounting, electrical installation, start-up and maintenance of this instrument may only be carried out by trained personnel authorized by the operator of the facility. Personnel must read and understand this Operating Manual before carrying out its instructions. ...
Page 21 4.4. INSTALLING THE HARDWARE 4.4.1. INTRODUCTION Electro static discharge does inflict irreparable damage to electronics! Before installing or opening the unit, the installer has to discharge himself by touching a well-grounded object. This unit must be installed in accordance with the EMC guidelines (Electro Magnetic Compatibility). Aluminum enclosures When installed in an aluminum enclosure and a potentially explosive atmosphere requiring apparatus of equipment protection level Ga and Da, the unit must be installed such that, even in the...
Page 22 4.4.2. VOLTAGE SELECTION SENSOR SUPPLY For Intrinsically Safe applications: read chapter 5. Type PB / PC / PX (AP) - battery powered and output loop-powered applications: Terminal 11 provides a limited supply voltage of 3 V DC (coil signals 1.2V) for the signal output of the flowmeter.
Page 23 4.4.3. TERMINAL CONNECTORS For Intrinsically Safe applications: read chapter 5. The following terminal connectors are available: PD / PF/ PM / PX Power supply Fig. 10: Overview of terminal connectors standard configuration F113-A and options. REMARKS: TERMINAL CONNECTORS: Power Supply: Terminal GND- 01- 02 only available with type PD / PF or PM: erminal SENSOR SUPPLY...
Page 24
Page 24 Terminal 03-04; alarm / pulse output R2: This output is always a fast output. With SETUP 8, the function of this output is set to a flowrate alarm output or pulse output. If pulse output function is selected: the maximum pulse frequency of this output is 500Hz. If a relay output option has been supplied, be sure that the output frequency does not exceed 0.5Hz else the life-time of the relay will be reduced significantly.
Page 25
Page 25 Type OT: A passive transistor output is available with this option. Max. driving capacity 300mA@50V DC. Terminal 07-08 POWER SUPPLY type PX - output loop powered: Connect an external power supply of 8-30VDC to these terminals or a 4-20mA loop. For a DC supply: connect the "-"...
Page 26
Page 26 Type AB: An active 0-20mA signal proportional to the flowrate is available with this option. Max. driving capacity 1000 Ohm @ 24VDC. (Requires power supply type PD / PF / PM). Type AF: For the Intrinsically Safe floating 4-20mA signal: please read Chapter 5. Type AI: An isolated 4-20mA signal proportional to the flowrate is available with this option.
Page 27
Page 27 Type AU: A 0-10VDC signal proportional to the flowrate is available with this option. Max. load 10mA @ 10VDC. (Requires power supply type PD / PF / PM). Terminal 09-11: Type A – Flowmeter input (general) The F113-A requires a (0)4-20mA flowmeter signal which will be processed 4 times a second with a 14 bits accuracy.
Page 28
Page 28 Type IB - Terminal 12-13; external reset: With this function the total can be reset to zero with an external switch. The Total resets only when the switch opens. When closed Total still counts but the ”Clear Total” function is disabled (see chapter 2).
Page 29
Page 29 Terminal 26 - 31: type CB / CH / CI / CT - communication RS232 / RS485 / TTL: see the manufacturer's plate. Full serial communications and computer control in accordance with RS232 (length of cable max. 15 meters) or RS485 (length of cable max. 1200 meters) is possible. ...
Please Note Certificates, safety values and declaration of compliance can be found in the document named: “Fluidwell F1..-..-XI - Documentation for Intrinsic Safety”. Special conditions for safe use mentioned in both the certificate and the installation instructions must be observed for the connection of power to both input and / or output circuits.
Indicated labels on the back cover (below) and on the inside cover (right) show the type labels for intrinsically safe certified units. For details on usage see the separate “Fluidwell F1..-..-IX Documentation for Intrinsic Safety”. Serial number and year of production This information can be looked-up on the display: See setup function (par.
Page 32
Page 32 Explanation Intrinsically Safe options: Type AF - Intrinsically Safe floating 4-20mA analog output: A floating 4-20mA signal proportional to the flowrate is available with this option. When the output is disabled, a 3.5mA signal will be generated. Max. driving capacity 1000 Ohm @ 30V DC. Type PD - Intrinsically Safe power supply and sensor supply - Terminal GND- 01 and 11.
Page 33 CONFIGURATION EXAMPLES Configuration example IIB /IIIC F113-A-AP-IB-CT-OT-(PD)-XI HAZARDOUS AREA SAFE AREA TERMINAL CONNECTORS F100-series Modbus communication type CT: TTL I.S. Certified Isolator TTL to: = max. 30 V e.g. PC RS232 = max. 250 mA RS422 = max. 0.85 W +12V For example: Common ground...
Page 34
Page 34 Configuration example IIB/IIIC and IIC - F113-P-AP-IB-(CT)-OT-PD-XI HAZARDOUS AREA SAFE AREA TERMINAL CONNECTORS F100-series Modbus communication type CT: TTL Please note: communciation type CT is allowed in IIC applications. I.S. Certified Isolator TTL to: = max. 30 V e.g.
Batteries for use in safe areas have no Ex label. DO NOT EXCHANGE: Using the wrong type of battery can pose a SERIOUS RISK. For use in hazardous areas Fluidwell recommends FW-LiBAT batteries (manufactured by Fluidwell bv) only. Battery replacement procedure Depending on the production batch, one of two visualized Intrinsically Safe certified battery types may have been installed in the unit.
Page 36 MAINTENANCE 6.1. GENERAL DIRECTIONS Mounting, electrical installation, start-up and maintenance of the instrument may only be carried out by trained personnel authorized by the operator of the facility. Personnel must read and understand this Operating Manual before carrying out its instructions. The F113-A may only be operated by personnel who are authorized and trained by the operator of the facility.
Page 37
Page 37 APPENDIX A: TECHNICAL SPECIFICATION GENERAL Display Type High intensity reflective numeric and alphanumeric LCD, UV-resistant. Digits Seven 17mm (0.67") and eleven 8mm (0.31"). Various symbols and measuring units. Refresh rate User definable: 8 times/sec - 30 secs. Type ZB LCD with green LED backlight.
Page 38
Page 38 Data protection Type EEPROM backup of all setting. Backup of running totals every minute. Data retention at least 10 years. Password Configuration settings can be password protected. Hazardous area (option) Intrinsically safe ATEX approval: Type XI II 1 G Ex ia IIB/IIC T4 Ga II 1 D Ex ia IIIC T100°C Da IP6x IECEx approval: Ex ia IIB/IIC T4 Ga...
Page 39
Page 39 Alarm outputs Function User defined: flowrate alarm or pulse output. Alarm output lo-lo; lo; hi; hi-hi flow rate alarm Pulse output Max. frequency 500Hz. Pulse length user definable. Type OA Three active 24V DC output; max. 50mA per output (requires type PD, PF or PM). Type OR Two electro-mechanical relay outputs;...
Page 40
Page 40 APPENDIX B: PROBLEM SOLVING In this appendix, several problems are included that can occur when the F113-A is going to be installed or while it is in operation. Flowmeter does not generate pulses: Check: Signal selection SETUP - 61, ...
Page 41
0x0000.0002.6CD0 = 158928. If this value needs to be calculated: 0*65536*65536 + 2*65536 + 27856 = 158928. For additional information regarding using your Fluidwell Modbus device, please read the ‘Fluidwell General Modbus Communication Protocol’ and ‘Modbus troubleshooting guide’ that are available through our website or your distributor.
Page 42
Page 42 REGISTER TYPE VALUE / REMARKS VARIABLE ADDRESS TOTAL REGISTERS 40033 unit uint16 0=none 0x020 3=kg 4=lb 5=gal 6 =usgal 7=bbl 40034 decimals uint16 0…3 0x021 40035 Span uint32 0.000001 – 9999999 unit / second 0x022 40038 Decimals span uint16 0 …...
Page 44
Page 44 REGISTER TYPE VALUE / REMARKS VARIABLE ADDRESS OTHERS REGISTERS 40161 model number uint16 113 0x0A0 40174 type uint16 ‘A’ 0x0AD 40163 firmware version uint32 0…999999 0x0A2 Representation: xx.xx.xx 40166 serial number uint32 0…9999999 0x0A5 40169 password uint16 0…9999 0x0A8 OTHER F113-A VARIABLES FOR COMMUNICATION TOTAL - variable number 566 (236h) –...
Page 45
Page 45 APPENDIX D: DECLARATION OF CONFORMITY FW_F113-A_v0601_01_EN...
Page 46
Page 46 INDEX OF THIS MANUAL accumulated Total ......... 8 Installation............ 18 actual settings ..........47 Intrinsic safety ..........32 analog Intrinsically Safe options ......34 0-10V output ..........27 IP classification ..........18 floating output..........34 keys ............... 7 flowrate min.
Page 47
Page 47 LIST OF CONFIGURATION SETTINGS SETTING DEFAULT DATE DATE 1 - TOTAL Enter your settings here 11 unit 12 decimals 0000000 13 span 1600 14 decimals span 2 - FLOWRATE 21 unit 22 time /sec 23 decimals 0000000 24 span 1600 25 decimals span 3 - ALARM...
Page 48
Page 48 LIST OF CONFIGURATION SETTINGS SETTING DEFAULT DATE DATE 9 - COMMUNICATION 91 speed 9600 92 address 93 mode BUS-RTU 94 databits 8 bits 95 parity none A - OTHERS A1 model F113-A F113-A F113-A A2 software version 03.nn.nn A3 serial nr nnnnnnn A4 password...
Page 49
Page 49 .nn.nn Fluidwell B.V. FW_F113-A_v0601_01_EN PO box 6 Voltaweg 23 Website: www.fluidwell.com 5460 AA Veghel 5466 AZ Veghel Find your nearest representative: www.fluidwell.com/representatives The Netherlands The Netherlands Copyright Fluidwell BV - 2016 - FW_F113-A_v0601_01_EN...