PRESSURE INDICATOR
Signal input sensor: (0)4-20mA.
Options: Intrinsically Safe.
F-Series - Field mounted indicators for safe and hazardous areas.
F-Series - Field mounted indicators for safe and hazardous areas. More info: www.fluidwell.com/fseries
More info: www.fluidwell.com/fseries

Advertisement

Table of Contents
loading

Summary of Contents for Fluidwell F Series

  • Page 1 F050-A PRESSURE INDICATOR Signal input sensor: (0)4-20mA. Options: Intrinsically Safe. F-Series - Field mounted indicators for safe and hazardous areas. F-Series - Field mounted indicators for safe and hazardous areas. More info: www.fluidwell.com/fseries More info: www.fluidwell.com/fseries...
  • Page 2: Safety Instructions

    115-230V AC power-supply type PM. The green / yellow wire between the back-casing and removable terminal-block may never be removed. ▪ Intrinsically Safe applications: follow the instructions as mentioned in Chapter 5 and consult “Fluidwell F0..-..-XI - Documentation for Intrinsic Safety”. DISPOSAL ▪...
  • Page 3: About The Operation Manual

    Manual FW-F050-A-M_v0403_04_EN.docx © 2019 Fluidwell bv - The Netherlands. Information in this manual is subject to change without prior notice. The manufacturer is not responsible for mistakes in this material or for incidental damage caused as a direct or indirect result of the delivery, performance or use of this material.
  • Page 4: Table Of Contents

    Page 4 CONTENTS MANUAL Safety instructions ..........................2 Disposal ............................2 Safety rules and precautionary measures .................... 2 About the operation manual ......................... 3 Contents manual ........................... 4 Introduction ........................5 Operational ........................6 Configuration ........................8 Installation ........................15 Intrinsically safe applications ..................
  • Page 5: Introduction

    Page 5 INTRODUCTION 1.1. SYSTEM DESCRIPTION OF THE F050-A Functions and features The pressure indicator model F050-A is a microprocessor driven instrument designed to display pressure. This product has been designed with a focus on: ▪ ultra-low power consumption to allow long-life battery powered applications (type PB / PC), ▪...
  • Page 6: Operational

    Page 6 OPERATIONAL 2.1. GENERAL ▪ The F050-A may only be operated by personnel who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed. ▪ Take careful notice of the " Safety rules, instructions and precautionary measures " in the front of this manual.
  • Page 7 Page 7 2.3. OPERATOR INFORMATION AND FUNCTIONS In general, the F050-A will always act at Operator level. The information displayed is dependant upon the SETUP-settings. The signal generated by the connected sensor is measured by the F050-A in the background, whichever screen refresh rate setting is chosen. After pressing a key, the display will be updated very quickly during a 30 second period, after which it will slow-down again.
  • Page 8: Configuration

    Page 8 CONFIGURATION 3.1. INTRODUCTION This and the following chapters are exclusively meant for electricians and non-operators. In these, an extensive description of all software settings and hardware connections are provided. ▪ Mounting, electrical installation, start-up and maintenance of the instrument may only be carried out by trained personnel authorized by the operator of the facility.
  • Page 9 Page 9 Matrix structure SETUP-level: SCROLLING THROUGH SETUP-LEVEL Selection of function-group and function: SETUP is divided into several function groups and functions. Each function has a unique number, which is displayed below the word "SETUP" at the bottom of the display. The number is a combination of two figures. The first figure indicates the function-group and the second figure the sub-function.
  • Page 10 Page 10 To change or select a value: To change a value, use  to select the digits and  to increase that value. If the new value is invalid, the increase sign or decrease-sign will be displayed while you are programming.
  • Page 11 Page 11 3.2.2. OVERVIEW FUNCTIONS SETUP LEVEL SETUP FUNCTIONS AND VARIABLES PRESSURE UNIT mbar - bar - PSI - mPA - PA - no unit DECIMALS 0 - 1 - 2 - 3 - 4 - 5 (Ref: displayed value) SPAN 0.00001 - 199,999 unit OFFSET...
  • Page 12 Page 12 2 - DISPLAY BARGRAPH The bargraph (piegraph) displayed at operator level is percentage-wise related to the input signal: minimum signal is 0% (setup 43) and maximum signal is 100% (setup 44). With this function, the bargraph can be enabled / disabled. Following selections are available: OFF - ON The functions below will only effect the optional LED-backlight.
  • Page 13 Page 13 4 - SENSOR FILTER The analog output signal of a sensor does mirror the actual pressure. This signal is measured several times a second by the F050-A. The value measured is a "snap-shot" of the real pressure as it will be fluctuating. With the help of this digital filter a stable and accurate reading can be obtained while the filter level can be set to a desired value.
  • Page 14 Page 14 4 - SENSOR (CONTINUED) TUNE MAX / 20MA With this setting it is possible to calibrate the input value for 20mA as the signal from the sensor might not be exact 20.0 mA at maximum pressure. This function will measure the real output value at maximum pressure. ▪...
  • Page 15: Installation

    Page 15 INSTALLATION 4.1. GENERAL DIRECTIONS ▪ Mounting, electrical installation, start-up and maintenance of this instrument may only be carried out by trained personnel authorized by the operator of the facility. Personnel must read and understand this Operating Manual before carrying out its instructions. ▪...
  • Page 16 Page 16 4.3. DIMENSIONS- ENCLOSURE Aluminum enclosures: 75 mm (2.95") 112 mm (4.40") 130 mm (5.12") 12mm 12mm 30mm 30mm 24mm 24mm M20 x 1,5 6 x M12 36mm 36mm 30mm 30mm M16 x 1,5 M16 x 1,5 1/2"NPT M20 x 1,5 0.12"...
  • Page 17 Page 17 GRP enclosures: 75 mm (2.95") 112 mm (4.40") 130 mm (5.12") HK back box: (flat bottom) 75 mm (2.95") 118 mm (4.65”) 25mm 25mm D=20mm D=20mm 12mm 12mm 30mm 30mm 24mm 24mm D=12mm D=16mm D=16mm D=20mm 36mm 36mm 0.12”...
  • Page 18 Page 18 4.4. INSTALLING THE HARDWARE 4.4.1. INTRODUCTION ▪ Electro static discharge does inflict irreparable damage to electronics! Before installing or opening the unit, the installer has to discharge himself by touching a well-grounded object. ▪ This unit must be installed in accordance with the EMC guidelines (Electro Magnetic Compatibility).
  • Page 19 Page 19 4.4.2. TERMINAL CONNECTORS WITH POWER SUPPLY - TYPE : PB / PD / PL / PX For Intrinsically Safe applications: read chapter 5. The following terminal connectors are available: SENSOR SIGNAL POWER SUPPLY SENSOR POWER SUPPLY ANALOG INPUT UNIT SUPPLY BACKLIGHT...
  • Page 20 Page 20 Terminal 4-5: POWER SUPPLY UNIT - TYPE PD / PX: To power the unit an internal battery can be used (type PB) and / or an external DC power supply of 8-30V DC (type PX) or 16-30V DC (type PD). Connect the "-"...
  • Page 21 Page 21 PF / PM Fig. 10: switch position voltage selection (type PF and PM). Switch positions / sensor supply voltage: VOLTAGE SELECTION 8.2V DC 12V DC 24V DC SWITCH on or off REMARKS: TERMINAL CONNECTORS: Terminal GND- 01- 02; POWER SUPPLY only available with type PF / PM: erminal PTION SENSOR SUPPLY...
  • Page 22: Intrinsically Safe Applications

    Safety Instructions ▪ Certificates, safety values, control drawing and declaration of compliance can be found in the document named: “Fluidwell F0..-A-XI - Documentation for Intrinsic Safety”. ▪ For installation under ATEX directive: this intrinsically safe device must be installed in accordance with the Atex directive 94/9/EC and the product certificate KEMA 05ATEX1168 X.
  • Page 23 FWCD-0001. Tamb CSA Certificate nr: CSA.08.2059461 – FM Project ID: 3033306 -40°C ... +70°C Made in Veghel, The Netherlands by Fluidwell bv -40°F ... +158°F KEMA 05ATEX1168 X Battery powered applications: II 1 G Ex ia IIC T4 Replace with certified II 1 D Ex iaD 20 IP 65 / 67 T 100°C...
  • Page 24 Page 24 5.2. TERMINAL CONNECTORS INTRINSICALLY SAFE APPLICATIONS: Terminal connectors F050-A-(PC / PD / PL / PX)-XI-(ZB): SENSOR SIGNAL POWER SUPPLY SENSOR POWER SUPPLY ANALOG INPUT UNIT SUPPLY BACKLIGHT TYPE: A (0)4-20mA TYPE: PD / PX TYPE: PD OPTION: ZB Fig.
  • Page 25 Page 25 Configuration example no. 2 Configuration example IIA - IIB and IIC application - F050-A-PD-XI-ZB HAZARDOUS AREA SAFE AREA TERMINAL CONNECTORS F0-series = max. 30 V Power supply Supply backlight = max. 200 mA Backlight option: type ZB For example = max.
  • Page 26 Page 26 5.4. BATTERY REPLACEMENT INSTRUCTIONS SAFETY INSTRUCTIONS • Handle the battery with care. A mistreated battery can become unsafe. Unsafe batteries can cause (serious) injury to persons. • Only use batteries which are certified for use in hazardous areas. The use of standard batteries in hazardous area's is not safe and prohibited.
  • Page 27: Maintenance

    Page 27 MAINTENANCE 6.1. GENERAL DIRECTIONS ▪ Mounting, electrical installation, start-up and maintenance of the instrument may only be carried out by trained personnel authorized by the operator of the facility. Personnel must read and understand this Operating Manual before carrying out its instructions. ▪...
  • Page 28: Appendix A: Technical Specification

    Page 28 APPENDIX A: TECHNICAL SPECIFICATION GENERAL Display Type High intensity reflective numeric and alphanumeric LCD, UV-resistant. Digits 5 ½ 26mm (1") and eleven 8mm (0.31"). Various symbols and measuring units. Piegraph 10 segment range indication in relation to its measuring range 0-100% Refresh rate User definable: 8 times/sec - 30 secs.
  • Page 29 Page 29 Sensor excitation Type PB / PC / PL / PX Sensor supply not available. Type PD As connected power supply voltage (internally linked) Type PF / PM Sensor supply voltage 8.2, 12 and 24V DC - max. 400mA@24V DC Terminal connections Type: Removable plug-in terminal strip.
  • Page 30: Appendix B: Problem Solving

    Page 30 APPENDIX B: PROBLEM SOLVING In this appendix, several problems are included that can occur when the F050-A is going to be installed or while it is in operation. Pressure displays "0 / zero" while a higher signal is available: Check: ▪...
  • Page 31: Appendix C: Declaration Of Conformity

    Page 31 APPENDIX C: DECLARATION OF CONFORMITY FW-F050-A-M_v0403_04_EN.docx...
  • Page 32: Appendix D: Control Drawing

    Page 32 APPENDIX D: CONTROL DRAWING FW-F050-A-M_v0403_04_EN.docx...
  • Page 33: Index Of This Manual

    Page 33 INDEX OF THIS MANUAL actual settings manual version alarm 7, 30 model backlight operational color operator level density pass code 14, 30 bargraph Piegraph 7, 12 battery life time 12, 27 power supply 20, 21 Battery replacement pressure configuration decimals contents...
  • Page 34: Notes

    Page 34 NOTES FW-F050-A-M_v0403_04_EN.docx...
  • Page 35 Page 35 NOTES FW-F050-A-M_v0403_04_EN.docx...
  • Page 36 54 pass code 0000 55 tagnumber 0000000 Fluidwell bv FW-F050-A-M_v0403_04_EN.docx PO box 6 Voltaweg 23 Website: www.fluidwell.com 5460 AA Veghel 5466 AZ Veghel Find your nearest representative: www.fluidwell.com/representatives The Netherlands The Netherlands Copyright Fluidwell bv - © 2019 - FW-F050-A-M_v0403_04_EN.docx...