Fluidwell F118-A Manual

Fluidwell F118-A Manual

Flowrate indicator / totalizer with linearisation and high / low alarms

Advertisement

Quick Links

F118-A
FLOWRATE INDICATOR / TOTALIZER
WITH LINEARISATION AND HIGH / LOW ALARMS
Signal input flowmeter: (0)4-20mA
Analog output: 4-20mA ref. flowrate and pulse ref. total.
Switch outputs: high / low alarms and / or pulse ref. total.
Options: Intrinsically Safe, Modbus communication.
F-Series - Field mounted indicators for safe and hazardous areas. More info: www.fluidwell.com/fseries

Advertisement

Table of Contents
loading

Summary of Contents for Fluidwell F118-A

  • Page 1: Safety Instructions

    Signal input flowmeter: (0)4-20mA Analog output: 4-20mA ref. flowrate and pulse ref. total. Switch outputs: high / low alarms and / or pulse ref. total. Options: Intrinsically Safe, Modbus communication. F-Series - Field mounted indicators for safe and hazardous areas. More info: www.fluidwell.com/fseries...
  • Page 2: Safety Rules And Precautionary Measures

     Any responsibility is lapsed if the instructions and procedures as described in this manual are not followed.  LIFE SUPPORT APPLICATIONS: The F118-A is not designed for use in life support appliances, devices, or systems where malfunction of the product can reasonably be expected to result in a personal injury.
  • Page 3: About The Operation Manual

    This operation manual describes the standard unit as well as most of the options available. For additional information, please contact your supplier. A hazardous situation may occur if the F118-A is not used for the purpose it was designed for or is used incorrectly. Please carefully note the information in this operating manual indicated by the pictograms: A "warning"...
  • Page 4: Table Of Contents

    Safety rules and precautionary measures ....................... 2 About the operation manual ..........................3 Contents manual .............................. 3 Introduction ..........................5 1.1. System description of the F118-A ..................5 Operational ..........................7 2.1. General ..........................7 2.2. Control panel .......................... 7 2.3.
  • Page 5: Introduction

    This manual describes the unit with a analog type input from the flowmeter "-A version". Other versions are available to process pulses or 0-10V flowmeter signals. One flowmeter with a (0)4-20mA signal output can be connected to the F118-A. To power the sensor, several options are available.
  • Page 6 Page 6 Configuration of the unit The F118-A was designed to be implemented in many types of applications. For that reason, a SETUP-level is available to configure your F118-A according to your specific requirements. SETUP includes several important features, such as K-factors, measurement units, signal selection etc.
  • Page 7: Operational

     Take careful notice of the " Safety rules, instructions and precautionary measures " in the front of this manual. This chapter describes the daily use of the F118-A. This instruction is meant for users / operators. 2.2. CONTROL PANEL The following keys are available: Fig.
  • Page 8: Operator Information And Functions

    SETUP-settings. All pulses generated by the connected flowmeter are measured by the F118-A in the background, whichever screen refresh rate setting is chosen. After pressing a key, the display will be updated very quickly during a 30 second period, after which it will slow-down again.
  • Page 9 Page 9  Programming the flowrate alarm values Note: This function might not be immediately accessible due to a configuration setting. When the SELECT-key is pressed a few times, following flowrate alarm values are displayed:  low flowrate alarm: enter here 40 L/min for example, ...
  • Page 10: Configuration

    Operating Manual before carrying out its instructions.  The F118-A may only be operated by personnel who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed.
  • Page 11 Page 11 Matrix structure SETUP-level: SCROLLING THROUGH SETUP-LEVEL Selection function-group and function: SETUP is divided into several function groups and functions. Each function has a unique number, which is displayed below the word "SETUP" at the bottom of the display. The number is a combination of two figures. The first figure indicates the function-group and the second figure the function.
  • Page 12 Page 12 To change or a select a value or value: To change a value, use  to select the digits and  to increase that value. To select a setting, both  and  can be used. When the new value is not valid, the increase sign or decrease-sign will be displayed while you are programming.
  • Page 13: Overview Functions Setup Level

    Page 13 3.2.2. OVERVIEW FUNCTIONS SETUP LEVEL SETUP FUNCTIONS AND VARIABLES TOTAL UNIT L - m3 - kg - lb - GAL - USGAL - bbl - no unit DECIMALS 0 - 1 - 2 - 3 (Ref: displayed value) SPAN 0.000001 - 999,999 unit/second DECIMALS SPAN...
  • Page 14: Explanation Setup-Functions

    Page 14 3.2.3. EXPLANATION SETUP-FUNCTIONS 1 - TOTAL MEASUREMENT UNIT SETUP - 11 determines the measurement unit for total, accumulated total and pulse output. The following units can be selected: L - m3 - kg - lb. - GAL - USGAL - bbl - _ (no unit). Alteration of the measurement unit will have consequences for operator and SETUP-level values.
  • Page 15: Flowrate

    Page 15 2 - FLOWRATE The settings for total and flowrate are entirely separate. In this way, different units of measurement can be used for each e.g. cubic meters for total and liters for flowrate. The display update time for flowrate is one second or more. Note: these settings also influence the analog output.
  • Page 16: Alarm

    When used with the internal battery option, the user may hold the concern of reliable measurement over a long period of time. The F118-A has several smart power management functions to extend the battery life time significantly. Two of these functions can be set:...
  • Page 17: Flowmeter

    The analog output signal of a flowmeter does mirror the actual flow. This FILTER signal is measured several times a second by the F118-A. The value measured is a "snap-shot" of the real flow as it will be fluctuating. With the help of this digital filter a stable and accurate reading can be obtained while the filter level can be set to a desired value.
  • Page 18: Flowmeter (Continued)

    Page 18 5 - FLOWMETER (CONTINUED) CUT-OFF To ignore e.g. leakage of the flow or vibration, a low-flow cut-off can be set as percentage over the full range of 16mA (or 20mA / 10V). When the analog value is less then required with this setting, the signal will be ignored.
  • Page 19: Linearisation

    Page 19 6 - LINEARISATION The linearisation function is available to approach the real flowcurve better as with the general Span entered with setup 14 and 24. This to obtain a more accurate flowrate, total and accumulated total as well as the analog and pulse output at any flowmeter signal. A maximum of 15 linearisation-positions can be entered while the interpolation will calculate any other position in-between.
  • Page 20: Linearisation (Continued)

    Page 20 6 - LINEARISATION (CONTINUED) PERCENTAGE / The percentage is displayed at the bottom line of the display. M-FACTOR With value 0% the M-Factor is disabled. 61 TO 6A The M-Factor is displayed at the top-line of the display. The minimum value to be entered is 0.000001 and the maximum value is 9.999999.
  • Page 21: Relay Output

    1200 - 2400 - 4800 - 9600 baud BUS ADDRESS For communication purposes, a unique identity can be attributed to every F118-A. This address can vary from 1-255. MODE The communication can only be executed according Modbus protocol RTU mode (ASCII is not available for this model).
  • Page 22: A - Others

    TYPE OF MODEL For support and maintenance it is important to have information about the characteristics of the F118-A. Your supplier will ask for this information in the case of a serious breakdown or to assess the suitability of your model for upgrade considerations.
  • Page 23: Installation

    Personnel must read and understand this Operating Manual before carrying out its instructions.  The F118-A may only be operated by personnel who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed. ...
  • Page 24: Dimensions- Enclosure

    Page 24 4.3. DIMENSIONS- ENCLOSURE Aluminum enclosures: 75 mm (2.95") 112 mm (4.40") 130 mm (5.12") 12mm 12mm 30mm 30mm 24mm 24mm M20 x 1,5 6 x M12 36mm 36mm 30mm 30mm M16 x 1,5 M16 x 1,5 1/2"NPT M20 x 1,5 0.12"...
  • Page 25 Page 25 GRP enclosures: 75 mm (2.95") 112 mm (4.40") 130 mm (5.12") HK back box: (flat bottom) 75 mm (2.95") 118 mm (4.65”) 25mm 25mm D=20mm D=20mm 12mm 12mm 30mm 30mm 24mm 24mm D=12mm D=16mm D=16mm D=20mm 36mm 36mm 0.12”...
  • Page 26: Installing The Hardware

     Do ground the aluminum enclosure properly as indicated, if the F118-A has been supplied with the 115-230V AC power-supply type PM. The green / yellow wire between the back-casing and removable terminal-block may never be removed.
  • Page 27: Voltage Selection Sensor Supply

    Page 27 4.4.2. VOLTAGE SELECTION SENSOR SUPPLY For Intrinsically Safe applications: read chapter 5. Battery powered and output-loop powered applications: Terminal 11 offers a supply voltage of 3.2 V DC (coil signals 1.2V) for the signal output of the flowmeter. Note: This voltage MAY NOT be used to power the flowmeters electronics, converters etc.
  • Page 28: Terminal Connectors

    For Intrinsically Safe applications: read chapter 5. The following terminal connectors are available: Fig. 10: Overview of terminal connectors standard configuration F118-A and options. REMARKS: TERMINAL CONNECTORS: Power Supply: Terminal GND- 01- 02 only available with type PD, PF or PM:...
  • Page 29 Page 29 Terminal 03-04; transistor type OT - output R2: This output is always a fast output. With SETUP 8, the function of this output is set to a flowrate alarm output or pulse output. If pulse output function is selected: the maximum pulse frequency of this output is 60Hz. If a relay output option has been supplied, be sure that the output frequency does not exceed 5Hz or else the life-time of the relay will be reduced significantly.
  • Page 30 Page 30 Type OR: A mechanical relay output flowrate alarm output or pulse output is available with this option. Max. switch power 240V 0,5A per output. (Requires power supply type PF / PM). Terminal 07-08 POWER SUPPLY type PX - output loop powered: Connect an external power supply of 8-24 volts AC or 8-30VDC to these terminals or a 4-20mA loop.
  • Page 31 Page 31 Type AA: An active 4-20mA signal proportional to the flowrate is available with this option. When the output is disabled, a 3.5mA signal will be generated on these terminals. Max. driving capacity 1000 Ohm @ 24VDC. (Requires power supply type PD / PF / PM). Type AB: An active 0-20mA signal proportional to the flowrate is available with this option.
  • Page 32 Max. load 10mA @ 10VDC. (Requires power supply type PD / PF / PM). Terminal 09-11: Type A – Flowmeter input (general) The F118-A requires a (0)4-20mA flowmeter signal which will be processed 4 times a second with a 14 bits accuracy. The input is not isolated.
  • Page 33 Page 33 Terminal 14-15; transistor output R3: This output is always a fast transistor output. With SETUP 8, the function of this output is set to a flowrate alarm output or pulse output. If used as a pulse output: the maximum frequency of this output is 60Hz. Type OA: An active 24V DC flowrate alarm output or pulse output is available with this option.
  • Page 34 Page 34 Terminal 26 - 31: communication RS232/RS485 - type CB / CH / CI / CT:  Full serial communications and computer control in accordance with RS232 (length of cable max. 15 meters) or RS485 (length of cable max. 1200 meters) is possible. ...
  • Page 35: Intrinsically Safe Applications

    Please Note  Certificates, safety values and declaration of compliance can be found in the document named: “Fluidwell F1..-..-XI - Documentation for Intrinsic Safety”.  Special conditions for safe use mentioned in both the certificate and the installation instructions must be observed for the connection of power to both input and / or output circuits.
  • Page 36: Terminal Connectors Intrinsically Safe Applications

    IIB/IIIC Terminal connectors F118-A-XI: ALARM ALARM OPTION PD: POWER SUPPLY PULSE PULSE 4-20mA SENSOR SIGNAL OPTION IB: OUTPUT 2 OUTPUT 1 OUTPUT (0)4-20mA INPUT RESET TOTAL RESET Fig. 12: Overview of Intrinisically Safe terminal connectors F118-A and options. HF118AEN_v0501_06...
  • Page 37 Page 37 Explanation Intrinsically Safe options: Option AF - Intrinsically Safe floating 4-20mA analog output: A floating 4-20mA signal proportional to the flowrate is available with this option. When the output is disabled, a 3.5mA signal will be generated. Max. driving capacity 1000 Ohm @ 30VDC. Option PD-XI - Intrinsically Safe power supply and sensor supply - Terminal GND- 01 and 11.
  • Page 38: Configuration Examples

    Page 38 CONFIGURATION EXAMPLES Configuration example IIB /IIIC F118-A-AF-CT-OT-(PB)-(PD)-XI HAZARDOUS AREA SAFE AREA TERMINAL CONNECTORS F100-series Modbus communication type CT: TTL I.S. Certified  Isolator TTL to: = max. 30 V e.g. PC RS232 = max. 250 mA RS422 = max. 0.85 W...
  • Page 39 Page 39 Configuration example IIB/IIIC and IIC - F118-A-AP-(CT)-OT-PD-XI HAZARDOUS AREA SAFE AREA TERMINAL CONNECTORS F100-series Modbus communication type CT: TTL Please note: communciation type CT is allowed in IIC applications. I.S. Certified  Isolator TTL to: = max. 30 V e.g.
  • Page 40: Battery Replacement Instructions

    Batteries for use in safe areas have no Ex label. DO NOT EXCHANGE: Using the wrong type of battery can pose a SERIOUS RISK.  For use in hazardous areas Fluidwell recommends FW-LiBAT batteries (manufactured by Fluidwell bv) only. Battery replacement procedure Depending on the production batch, one of two visualized Intrinsically Safe certified battery types may have been installed in the unit.
  • Page 41: Maintenance

    Operating Manual before carrying out its instructions.  The F118-A may only be operated by personnel who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed.
  • Page 42: Appendix A: Technical Specification

    Page 42 APPENDIX A: TECHNICAL SPECIFICATION GENERAL Display Type High intensity reflective numeric and alphanumeric LCD, UV-resistant. Digits Seven 17mm (0.67") and eleven 8mm (0.31"). Various symbols and measuring units. Refresh rate User definable: 8 times/sec - 30 secs. Type ZB Transflective LCD with green LED backlight.
  • Page 43 Page 43 Terminal connections Type: Removable plug-in terminal strip. Wire max. 1.5mm2 and 2.5mm2 (type PM / PF) Data protection Type EEPROM backup of all setting. Backup of running totals every minute. Data retention at least 10 years. Pass code Configuration settings can be pass code protected.
  • Page 44 Page 44 Transistor outputs Type OT three passive transistor outputs - not isolated. Load max. 50V DC - 300mA Function User defined: flowrate alarm or pulse output. Alarm output low flowrate, high flowrate or flowrate alarm (both). Pulse output Max. frequency 60Hz. Pulse length user definable between 7,8msec up to 2 seconds. Type OA Active 24V DC output;...
  • Page 45: Appendix B: Problem Solving

    Page 45 APPENDIX B: PROBLEM SOLVING In this appendix, several problems are included that can occur when the F118-A is going to be installed or while it is in operation. Flowmeter does not generate pulses: Check:  Signal selection SETUP - 51, ...
  • Page 46: Appendix C: Communication Variables

    Page 46 APPENDIX C: COMMUNICATION VARIABLES Remarks:  Below, an overview of the F118-A specific variables; other common variables are described in the standard table.  All numbers are decimal numbers, unless otherwise noted.  Following variables of the standard table (var00-var30) are not valid for this product and will be responded with value 1: var00, 03-05, 07,08, 16-22, 24, 26-29.
  • Page 47 Page 47 DESCRIPTION BYTES VALUE REMARKS minimum flowrate 0-9,9999 decimals: see 50 (32h) maximum flowrate 0-9,9999 decimals: see 50 (32h) delay time alarm 1…9,999 steps of 0.1 second min. flowrate delay time alarm 1…9,999 steps of 0.1 second max. flowrate edit flowrate alarm 0=operator 1=SETUP level...
  • Page 48 (A8h) tagnumber 0..9999999 Other vars: see standard table OTHER F118-A VARIABLES FOR COMMUNICATION TOTAL - variable number 566 (236h) – 6 bytes Read total: The value of total read using communication might differ from the value that appears on the display. This is due to the fact that the display can only display up to seven digits ( for example when two decimals are selected for total and total has a value of 123456,78 the display will show 23456,78 while communication will read a “total”...
  • Page 49: Index Of This Manual

    Fig. 8: Grounding aluminum enclosure with type PM 115-230V AC..........26 Fig. 9: switch position voltage selection (option PD and PM)............27 Fig. 10: Overview of terminal connectors standard configuration F118-A and options..... 28 Fig. 11: Overview terminal connectors communication option............34 Fig.
  • Page 50 Page 50 NOTES HF118AEN_v0501_06...
  • Page 51 Page 51 LIST OF CONFIGURATION SETTINGS SETTING DEFAULT DATE : DATE : 1 - TOTAL 11 unit 12 decimals 0000000 13 span 001600 /sec /sec /sec 14 decimals span 2 - FLOWRATE 21 unit 22 time unit /sec 23 decimals 0000000 24 span 001600 /min...
  • Page 52 A - OTHERS A4 password 0000 A5 tagnumber 0000000 Fluidwell bv HF118AEN_v0501_06 PO box 6 Voltaweg 23 Website: www.fluidwell.com 5460 AA Veghel 5466 AZ Veghel Find your nearest representative: www.fluidwell.com/representatives The Netherlands The Netherlands Copyright Fluidwell bv - 2014 - HF118AEN_v0501_06...