Fluidwell F Series Manual
Hide thumbs Also See for F Series:

Advertisement

Quick Links

F011-P
TOTALIZER
Signal input flowmeter: pulse, Namur and coil.
Options: Intrinsically Safe.
F-Series - Field mounted indicators for safe and hazardous areas.
F-Series - Field mounted indicators for safe and hazardous areas. More info: www.fluidwell.com/fseries
More info: www.fluidwell.com/fseries

Advertisement

Table of Contents
loading

Summary of Contents for Fluidwell F Series

  • Page 1 F011-P TOTALIZER Signal input flowmeter: pulse, Namur and coil. Options: Intrinsically Safe. F-Series - Field mounted indicators for safe and hazardous areas. F-Series - Field mounted indicators for safe and hazardous areas. More info: www.fluidwell.com/fseries More info: www.fluidwell.com/fseries...
  • Page 2: Safety Instructions

    ▪ Intrinsically Safe applications: follow the instructions as mentioned in Chapter 5 and consult “Fluidwell F0..-..-XI - Documentation for Intrinsic Safety”. DISPOSAL ▪ At the end of its life this product should be disposed of according to local regulations regarding waste electronic equipment.
  • Page 3: About The Operation Manual

    Manual FW-F011-P-M_v0403_04_EN.docx © 2019 Fluidwell bv - The Netherlands. Information in this manual is subject to change without prior notice. The manufacturer is not responsible for mistakes in this material or for incidental damage caused as a direct or indirect result of the delivery, performance or use of this material.
  • Page 4: Table Of Contents

    Page 4 CONTENTS MANUAL Safety instructions ..........................2 Disposal ............................2 Safety rules and precautionary measures .................... 2 About the operation manual ......................... 3 Contents manual ........................... 4 Introduction ........................5 Operational ........................6 Configuration ........................8 Installation ........................15 Intrinsically safe applications ..................
  • Page 5: Introduction

    Page 5 INTRODUCTION 1.1. SYSTEM DESCRIPTION OF THE F011-P Functions and features The flowrate / totalizer model F011-P is a microprocessor driven instrument designed to display a resettable total and non-resettable accumulated total. This product has been designed with a focus on: ▪...
  • Page 6: Operational

    Page 6 OPERATIONAL 2.1. GENERAL ▪ The F011-P may only be operated by personnel who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed. ▪ Take careful notice of the " Safety rules, instructions and precautionary measures" in the front of this manual.
  • Page 7 Page 7 2.3. OPERATOR INFORMATION AND FUNCTIONS In general, the F011-P will always function at Operator level. The information displayed is dependant upon the SETUP-settings. All pulses generated by the connected flowmeter are measured by the F011-P in the background, whichever screen refresh rate setting is chosen. After pressing a key, the display will be updated very quickly during a 30 second period, after which it will slow-down again.
  • Page 8: Configuration

    Page 8 CONFIGURATION 3.1. INTRODUCTION This and the following chapters are exclusively meant for electricians and non-operators. In these, an extensive description of all software settings and hardware connections are provided. ▪ Mounting, electrical installation, start-up and maintenance of the instrument may only be carried out by trained personnel authorized by the operator of the facility.
  • Page 9 Page 9 Matrix structure SETUP-level: SCROLLING THROUGH SETUP-LEVEL Selection of function-group and function: SETUP is divided into several function groups and functions. Each function has a unique number, which is displayed below the word "SETUP" at the bottom of the display. The number is a combination of two figures. The first figure indicates the function-group and the second figure the sub-function.
  • Page 10 Page 10 To change or select a value: To change a value, use  to select the digits and  to increase that value. If the new value is invalid, the increase sign or decrease-sign will be displayed while you are programming.
  • Page 11 Page 11 3.2.2. OVERVIEW FUNCTIONS SETUP LEVEL SETUP FUNCTIONS AND VARIABLES TOTAL UNIT L - m3 - kg - lb - GAL - USGAL - bbl - no unit DECIMALS 0 - 1 - 2 - 3 (Ref: displayed value) K-FACTOR: 0.000010 - 9,999,999 DECIMALS K-FACTOR...
  • Page 12 Page 12 3.2.3. EXPLANATION OF SETUP-FUNCTIONS 1 - TOTAL MEASUREMENT UNIT SETUP - 11 determines the measurement unit for total and accumulated total. The following units can be selected: L - m3 - kg - lb. - GAL - USGAL - bbl - _ (no unit). Alteration of the measurement unit will have consequences for operator and SETUP-level values.
  • Page 13 Page 13 2 - DISPLAY The functions below will only effect the optional LED-backlight. BACKLIGHT If a LED backlight has been supplied, the color can be selected. (OPTION) Following selections are available: OFF - GREEN - AMBER BRIGHTNESS The density of the backlight can be set in following range: (OPTION) 1 - 5 One is minimum and five is maximum brightness.
  • Page 14 Page 14 4 - FLOWMETER SIGNAL The F011-P is able to handle several types of input signal. The type of flowmeter pickup / signal is selected with SETUP 41. Read also par. 4.4.2. or 4.4.3 - flowmeter input terminals. TYPE OF SIGNAL EXPLANATION RESISTANCE FREQ...
  • Page 15: Installation

    Page 15 INSTALLATION 4.1. GENERAL DIRECTIONS ▪ Mounting, electrical installation, start-up and maintenance of this instrument may only be carried out by trained personnel authorized by the operator of the facility. Personnel must read and understand this Operating Manual before carrying out its instructions. ▪...
  • Page 16 Page 16 4.3. DIMENSIONS- ENCLOSURE Aluminum enclosures: 75 mm (2.95") 112 mm (4.40") 130 mm (5.12") 12mm 12mm 30mm 30mm 24mm 24mm M20 x 1,5 6 x M12 36mm 36mm 30mm 30mm M16 x 1,5 M16 x 1,5 1/2"NPT M20 x 1,5 0.12"...
  • Page 17 Page 17 GRP enclosures: 75 mm (2.95") 112 mm (4.40") 130 mm (5.12") HK back box: (flat bottom) 75 mm (2.95") 118 mm (4.65”) 25mm 25mm D=20mm D=20mm 12mm 12mm 30mm 30mm 24mm 24mm D=12mm D=16mm D=16mm D=20mm 36mm 36mm 0.12”...
  • Page 18 Page 18 4.4. INSTALLING THE HARDWARE 4.4.1. INTRODUCTION ▪ Electro static discharge does inflict irreparable damage to electronics! Before installing or opening the unit, the installer has to discharge himself by touching a well-grounded object. ▪ This unit must be installed in accordance with the EMC guidelines (Electro Magnetic Compatibility).
  • Page 19 Page 19 4.4.2. TERMINAL CONNECTORS WITH POWER SUPPLY - TYPE : PB / PD / PX For Intrinsically Safe applications: read chapter 5. The following terminal connectors are available: SENSOR SIGNAL POWER SUPPLY SENSOR POWER SUPPLY BACKLIGHT PULSE INPUT UNIT SUPPLY OPTION: ZB TYPE: P...
  • Page 20 Page 20 REMARKS: TERMINAL CONNECTORS: Terminals 1-3; Flowmeter input: Three basic types of flowmeter signals can be connected to the unit: pulse, active pulse or coil. The screen of the signal wire must be connected to the common ground terminal The input signal type has to be selected with the correct SETUP-function (read par.
  • Page 21 Page 21 Pulse-signal PNP / PNP-LP: The F011-P is suitable for use with flowmeters which have a PNP output signal. Terminal 3 offers 3.2V which has to be switched by the sensor to terminal 2 (SIGNAL). For a reliable pulse detection, the pulse amplitude has to go above 1.2V.
  • Page 22 Page 22 Reed-switch: The F011-P is suitable for use with flowmeters which have a reed-switch. To avoid pulse bounce from the reed-switch, it is advised to select REED LP - low-pass filter (read par. 3.2.3.) Reed - switch signal input INTERNAL EXTERNAL + 3.2V DC...
  • Page 23 Page 23 4.4.3. TERMINAL CONNECTORS WITH POWER SUPPLY - TYPE : PF / PM For Intrinsically Safe applications: read chapter 5. The following terminal connectors are available: POWER SUPPLY SENSOR SIGNAL TYPE: TYPE: P: PF / PM PULSE INPUT SIGNAL Fig.
  • Page 24 Page 24 REMARKS: TERMINAL CONNECTORS: Terminal GND- 01- 02 POWER SUPPLY only available with type PF / PM: erminal PTION SENSOR SUPPLY PF 24V AC  10% 1.2, 3.2, 8.2, 12, 24V max. 400mA@24V DC PF 24V DC  10% 1.2, 3.2, 8.2, 12, 24V max.
  • Page 25 Page 25 Pulse-signal NPN / NPN-LP: The F011-P is suitable for use with flowmeters which have a NPN output signal. For reliable pulse detection, the pulse amplitude has to go below 1.2V. Signal setting NPN-LP employs a low-pass signal noise filter, which limits the maximum input frequency - read par. 3.2.3. NPN signal input INTERNAL EXTERNAL...
  • Page 26 Page 26 Reed-switch: The F011-P is suitable for use with flowmeters which have a reed-switch. To avoid pulse bounce from the reed-switch, it is advised to select REED LP - low-pass filter (read par. 3.2.3.) Reed - switch signal input INTERNAL EXTERNAL + 3.2V DC...
  • Page 27: Intrinsically Safe Applications

    Safety Instructions ▪ Certificates, safety values, control drawing and declaration of compliance can be found in the document named: “Fluidwell F0..-P-XI - Documentation for Intrinsic Safety”. ▪ For installation under ATEX directive: this intrinsically safe device must be installed in accordance with the Atex directive 94/9/EC and the product certificate KEMA 05ATEX1168 X.
  • Page 28 FWCD-0003. Tamb CSA Certificate nr: CSA.08.2059461 – FM Project ID: 3033306 -40°C ... +70°C Made in Veghel, The Netherlands by Fluidwell bv -40°F ... +158°F KEMA 05ATEX1168 X Battery powered applications: II 1 G Ex ia IIC T4 Replace with certified II 1 D Ex iaD 20 IP 65 / 67 T 100°C...
  • Page 29 Page 29 5.3. CONFIGURATION EXAMPLES INTRINSICALLY SAFE APPLICATIONS: Configuration example no. 1 Configuration example IIA - IIB and IIC F011-P-PC-(PX)-XI-(ZB) - battery powered unit HAZARDOUS AREA SAFE AREA TERMINAL CONNECTORS F0-series Backlight option: type ZB Supply backlight (not used in this example). Common ground Basic power supply type PX: 8-30V DC...
  • Page 30 Page 30 Configuration example no. 3 Configuration example IIA - IIB and IIC application - F011-P-PD-XI-ZB HAZARDOUS AREA SAFE AREA TERMINAL CONNECTORS F0-series = max. 30 V Power supply Supply backlight = max. 200 mA Backlight option: type ZB For example = max.
  • Page 31 Page 31 5.4. BATTERY REPLACEMENT INSTRUCTIONS SAFETY INSTRUCTIONS • Handle the battery with care. A mistreated battery can become unsafe. Unsafe batteries can cause (serious) injury to persons. • Only use batteries which are certified for use in hazardous areas. The use of standard batteries in hazardous area's is not safe and prohibited.
  • Page 32: Maintenance

    Page 32 MAINTENANCE 6.1. GENERAL DIRECTIONS ▪ Mounting, electrical installation, start-up and maintenance of the instrument may only be carried out by trained personnel authorized by the operator of the facility. Personnel must read and understand this Operating Manual before carrying out its instructions. ▪...
  • Page 33: Appendix A: Technical Specification

    Page 33 APPENDIX A: TECHNICAL SPECIFICATION GENERAL Display Type High intensity reflective numeric and alphanumeric LCD, UV-resistant. Digits Seven 17mm (0.67") and eleven 8mm (0.31"). Various symbols and measuring units. Refresh rate User definable: 8 times/sec - 30 secs. Type ZB (option) Bi-color configurable LED-backlight - green or amber.
  • Page 34 Page 34 Sensor excitation Type PB / PC / PX Sensor supply voltage: 3.2V DC for pulse signals and 1.2V DC for coil pick-up. Please note: this is not a real sensor supply. Only suitable for sensors with a very low power consumption like coils (sine wave) and reed-switches.
  • Page 35: Appendix B: Problem Solving

    Page 35 OPERATIONAL Operator functions Displayed functions • total and accumulated total. • total can be reset to zero by pressing the CLEAR-key twice. Total Digits 7 digits. Units L, m3, GAL, USGAL, KG, lb, bbl, no unit. Decimals 0 - 1 - 2 or 3. Note total can be reset to zero.
  • Page 36: Appendix C: Declaration Of Conformity

    Page 36 APPENDIX C: DECLARATION OF CONFORMITY FW-F011-P-M_v0403_04_EN.docx...
  • Page 37: Appendix D: Control Drawing

    Page 37 APPENDIX D: CONTROL DRAWING FW-F011-P-M_v0403_04_EN.docx...
  • Page 38: Index Of This Manual

    Page 38 INDEX OF THIS MANUAL active pulse signal 21, 25 namur signal 22, 26 actual settings operational backlight operator level color pass code 14, 35 density power supply 22, 24 battery life time 13, 32 problem solving battery replacement pulse-signal NPN 20, 25 clear total...
  • Page 39: Notes

    Page 39 NOTES FW-F011-P-M_v0403_04_EN.docx...
  • Page 40 _ _ _ _ _ _ _ 54 pass code 0000 55 tagnumber 0000000 Fluidwell bv FW-F011-P-M_v0403_04_EN.docx PO box 6 Voltaweg 23 Website: www.fluidwell.com 5460 AA Veghel 5466 AZ Veghel Find your nearest representative: www.fluidwell.com/representatives The Netherlands The Netherlands Copyright Fluidwell bv - © 2019- FW-F011-P-M_v0403_04_EN.docx...