F-Series - Field mounted indicators for safe and hazardous areas.
F119-P
TOTALIZER WITH RECEIPT PRINTER DRIVER,
linearization, analog and pulse outputs
Signal input flowmeter: pulse, Namur and coil.
Signal outputs: analog 4-20mA reflecting flow rate, pulse
retransmission and scaled pulse reflecting total.
Options: Modbus communication, external reset and backlight.
FW-F119-P-M_v2001_02_EN.docx
More info: www.fluidwell.com/fseries.

Advertisement

Table of Contents
loading

Summary of Contents for Fluidwell F Series

  • Page 1 Signal input flowmeter: pulse, Namur and coil. Signal outputs: analog 4-20mA reflecting flow rate, pulse retransmission and scaled pulse reflecting total. Options: Modbus communication, external reset and backlight. F-Series - Field mounted indicators for safe and hazardous areas. FW-F119-P-M_v2001_02_EN.docx More info: www.fluidwell.com/fseries.
  • Page 2: Safety Instructions

    Page 2 SAFETY INSTRUCTIONS • Any responsibility is lapsed if the instructions and procedures as described in this manual are not followed. • LIFE SUPPORT APPLICATIONS: The F119-P is not designed for use in life support appliances, devices, or systems where malfunction of the product can reasonably be expected to result in a personal injury.
  • Page 3: About The Operation Manual

    Manual : FW-F119-P-M_v2001_02_EN.docx © Copyright 2020 : Fluidwell B.V. - the Netherlands Information in this manual is subject to change without prior notice. The manufacturer is not responsible for mistakes in this material or for incidental damage caused as a direct or indirect result of the delivery, performance or use of this material.
  • Page 4: Table Of Contents

    Page 4 CONTENTS MANUAL SAFETY INSTRUCTIONS ............................ 2 DISPOSAL OF ELECTRONIC WASTE ........................ 2 SAFETY RULES AND PRECAUTIONARY MEASURES ..................2 ABOUT THE OPERATION MANUAL........................3 WARRANTY AND TECHNICAL SUPPORT ......................3 CONTENTS MANUAL ............................4 INTRODUCTION ............................. 5 System description of the F119-P .................... 5 Ticket printing ...........................
  • Page 5: Introduction

    Page 5 1 INTRODUCTION SYSTEM DESCRIPTION OF THE F119-P Functions and features The flow rate / totalizer, model F119-P is a microprocessor driven instrument designed to linearize the flowmeters flow curve and to show flow rate, total and accumulated total. Additionally, the F119-P is capable of printing totalizer tickets and delivery tickets.
  • Page 6 Page 6 Standard outputs • Configurable pulse output to transmit pulses representing a certain linearized total quantity. The pulse length can be set as desired with a maximum frequency of 500Hz. • Unscaled frequency output for retransmission of the incoming pulses as robust square wave forms.
  • Page 7: Ticket Printing

    When the print command is given, a totalizer ticket as shown in below example is printed: ==================== Fluidwell F119 Header line 2 Configurable header Header line 3...
  • Page 8 (type IB). This is explained in Chapter 2. When a delivery is ended, a delivery ticket as shown in below example is printed: ==================== Fluidwell F119 Header line 2 Configurable header Header line 3...
  • Page 9: Operational

    Page 9 2 OPERATIONAL GENERAL INFORMATION This chapter describes the daily use of the F119-P. This instruction is meant for users / operators. • The F119-P may only be operated by personnel who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed. •...
  • Page 10 Page 10 For the Operator, the following functions are available: Display process values On the main screen, the primary process values of the F119-P are shown. By default, Total is shown on the upper-line of the display and Flowrate on the bottom line. In the configuration settings for Display, this can be changed to show only Flowrate on the large 12mm digits or to show Total and Accumulated Total simultaneously.
  • Page 11 Page 11 Ending a delivery will cause the following actions to be executed sequentially: 1. Increment last delivery number. 2. Register delivery number, current totalizer values and date / time stamp. 3. Clear the totalizer (this does not influence the value of Accumulated Total or Current Day Total) and immediately start a new delivery without losing totalizer counts.
  • Page 12: Operator Alarms

    Page 12 Display historical day totals Besides directly reviewing the Current Day Total and Previous Day Total, a list of the last 15 Previous Day Totals can be reviewed. To enter the list, press the CLEAR-key for 3 seconds. Use the SELECT- and CLEAR-key to scroll up and down through the list of Previous Day Totals.
  • Page 13: Configuration

    Page 13 3 CONFIGURATION INTRODUCTION This and the following chapters are exclusively meant for electricians and non-operators. In these, an extensive description of all software settings and hardware connections is provided. • Mounting, electrical installation, start-up and maintenance of the instrument may only be carried out by trained personnel authorized by the operator of the facility.
  • Page 14 Page 14 Use the control panel to navigate through SETUP-level PROG-key When a function is selected, this key is used to start the programming sequence. When only a function group is selected (and no function), this key is used to scroll back a function group (e.g.
  • Page 15 Page 15 Step 2b: Changing the selected item in a list SELECT-key This key is used to select the next item in the list (e.g. Disable → Enable). At the end of the list, the selection will wrap around to the first selection. CLEAR-key This key is used to select the previous item in the list (e.g.
  • Page 16: Configuration Settings

    Page 16 CONFIGURATION SETTINGS All settings of the F119-P can be set via the control panel. As an alternative, you can also use the Remote Configuration Software which you can find on our website or through your supplier. Depending on the type of communication interface your device has, you might need a specific communication cable, which is available through your supplier.
  • Page 17 Page 17 ANALOG OUTPUT enable – disable RATE-MIN (4mA) 0000000 – 9999999 RATE-MAX (20mA) 0000000 – 9999999 CUT-OFF 0.0 – 9.9% TUNE-MIN (4mA) 0000 – 9999 TUNE-MAX (20mA) 0000 – 9999 FILTER 1 – 99 PULSE MODE disable, scaled, retrans WIDTH 0.000 –...
  • Page 18 Page 18 EXPLANATION OF SETUP-MENU 1 – TOTAL 3.3.2 • First setup the flowmeter at SETUP MENU 5 - Flowmeter. It has a direct influence on the settings for Total. • Change of the type of flowmeter unit (SETUP 5.2 and SETUP 5.3) will cause the Total unit to jump to the default setting of the new flowmeter unit type.
  • Page 19 Page 19 EXPLANATION OF SETUP-MENU 2 – FLOWRATE 3.3.3 • First setup the flowmeter at SETUP MENU 5 - Flowmeter. It has a direct influence on the settings for Flowrate. • Change of the type of flowmeter unit (SETUP 5.2 and SETUP 5.3) will cause the flowrate unit to jump to the default setting of the new flowmeter unit type.
  • Page 20 Page 20 3.3.4 EXPLANATION OF SETUP-MENU 3 - DISPLAY DISPLAY FUNCTION This setting determines which information is shown on the main screen. The function can be set to indicate total, flowrate or accumulated total. • Total: Total is displayed with the large 12mm (0.47”) digits and flowrate is displayed with the 7 mm (0.28”) digits simultaneously.
  • Page 21 Page 21 EXPLANATION OF SETUP-MENU 5 – FLOWMETER 3.3.6 To simplify the configuration of the Flowmeter, total and flow rate settings, the F119-P is equipped with an automatic unit conversion feature. This avoids different K-Factor calculations for Total and Flowrate and all configuration it done inside the Flowmeter menu. To use the automatic unit conversion, you only need to enter the (average) K-Factor and the related measurement unit.
  • Page 22 Page 22 To make use of the automatic unit conversion, Total and Flowrate must have a convertible unit. If this is not possible, HAND should be chosen. This will cause SETUP 5.3 and SETUP 5.4 to disappear and the unit, K-factor and K-factor decimals must be specifically set at SETUP-menu 1 –...
  • Page 23 Page 23 The linearization function uses linearization points to calculate new K-factors based on the measured flowmeter frequency. As shown in the chart above, each point consists of a frequency and a Meter Factor (MFx, indicating the deviation of the K-factor KFx from the average K-factor KF0). When a new frequency is measured, the corresponding Meter Factor is calculated by interpolating between the linearization points.
  • Page 24 Page 24 3.3.8 EXPLANATION OF SETUP-MENU 7 - ANALOG OUTPUT An analog 4-20mA signal is generated according to the flowrate with a 12 bits resolution. The settings for Flowrate (SETUP-menu 2) influence the analog output directly and should be configured first.
  • Page 25 Page 25 FILTER The analog output signal is updated 8 times per second and an instable flowrate can cause a varying output current. With the help of this filter function a more stable but less precise output current can be obtained. The filter principal is based on three input values: filter level (01-99), previous filter value and actual flowrate.
  • Page 26 Page 26 WIDTH When scaled mode is selected for the pulse output, the pulse width determines the time that the output will be active, that is, the duration of the pulse. The pulse width is set in milliseconds in the range 0.001 –...
  • Page 27 Page 27 TRANSMIT DELAY This setting is used to configure and additional delay between receiving a Modbus message and transmitting the reply. The transmit delay is useful on communications busses to allow drivers to switch between transmitting and receiving, such as RS485. The delay can vary from 0-255 msec and is set to 15ms by default.
  • Page 28 Page 28 10.7 DAILY TOTAL If the daily total feature is activated in SETUP 3.2, this setting is used to print the Current Day Total and Previous Day Total on the totalizer ticket. The following can be selected: • No print – current and previous day totals are not printed. •...
  • Page 29: Installation

    Page 29 4 INSTALLATION GENERAL DIRECTIONS • Mounting, electrical installation, start-up and maintenance of this instrument may only be carried out by trained personnel authorized by the operator of the facility. Personnel must read and understand this Operating Manual before carrying out its instructions. •...
  • Page 30: Handling The F-Series Enclosure

    Page 30 HANDLING THE F-SERIES ENCLOSURE 4.3.1 IDENTIFICATION Identification label To identify your F1-Series device, all field mount enclosures have a weatherproof identification label placed on the outside of the unit. Fig. 11: Identification – Example of F1-Series identification label Installation label A second label is located on the inside and shows additional installation data.
  • Page 31 Page 31 4.3.2 OPENING / REMOVING THE COVER To open the F-Series enclosure, the front cover needs to be removed. Please follow this procedure: 1. If necessary, clean the enclosure with an anti-static cloth made damp with a mild soap solution. Wait for the enclosure to dry before opening.
  • Page 32: Mechanical Installation

    Page 32 MECHANICAL INSTALLATION DIMENSIONS – ALUMINUM ENCLOSURE – TYPE HA, HL…HZ, HAA … HAZ 4.4.1 Fig. 13: Dimensions – Aluminum enclosures DIMENSIONS – ALUMINUM W. EXTENDED BACK ENCLOSURE – TYPE HBA … HBZ 4.4.2 Fig. 14: Dimensions – Aluminum with extended back enclosures DIMENSIONS –...
  • Page 33 Page 33 4.4.5 MOUNTING The enclosure can be installed by itself or with the aid of a mounting plate in the configurations shown below. When the unit is installed on a wall or onto a meter, please use components and installation techniques that are suitable for the used materials.
  • Page 34: Electrical Installation

    Page 34 ELECTRICAL INSTALLATION • Electro static discharge does inflict irreparable damage to electronics! Before installing or opening the F119-P, the installer has to discharge himself by touching a well-grounded object. • The F119-P must be installed in accordance with the EMC guidelines (Electro Magnetic Compatibility).
  • Page 35 Inside of the Fluidwell unit, the various common ground terminals are connected to each other. It is advised to terminate the wire screens in the vicinity of the sensor and to insulate the wire screen with a shrink tube at the F119-P side.
  • Page 36 Page 36 4.5.4 POWER SUPPLY WIRING • The external power supply must be an approved ELV source, insulated from AC mains by double / reinforced insulation per CSA C22.2 No. 61010-1-12 / UL61010-1. The F119-P can be powered from an extern power supply or via the isolated 4-20mA current loop. An internal power supply is also available in the form of a lithium battery.
  • Page 37: Terminal Connectors

    Page 37 TERMINAL CONNECTORS Take careful notice of all safety and precautionary measures indicated in paragraph 4.4: Electrical Installation and review paragraph 4.4.3 and 4.4.4 before applying any field or power supply wiring. 4.6.1 OVERVIEW The following terminal connectors are available on the F119-P: Fig.
  • Page 38 Page 38 TERMINAL 07-08: ANALOG OUTPUT – TYPE AH 4.6.4 An analog output signal proportional to the flowrate is available as standard. The function of the analog output is determined by the settings of SETUP-menu 7: Analog output (see chapter 3). This output is a passive isolated 4-20mA output with the possibility to power the device via the 4-20mA loop.
  • Page 39 Page 39 Pulse-signal NPN / NPN-LP The F119-P is suitable for use with flowmeters which have a NPN output signal. For reliable pulse detection, the pulse amplitude has to go below 1.2V. Signal setting NPN-LP employs a low-pass signal noise filter, which limits the maximum input frequency (read chapter 3). Fig.
  • Page 40 Page 40 Reed-switch The F119-P is suitable for use with flowmeters which have a reed-switch. To avoid pulse bounce from the reed-switch, it is advised to select REED LP – low-pass filter (read chapter 3). Fig. 26: Terminal connections – Reed-switch signal input NAMUR-signal: The F119-P is suitable for flowmeters with an Namur signal.
  • Page 41 Page 41 4.6.7 TERMINAL C1-C6: COMMUNICATION INTERFACE The F119-P is equipped with a communication interface (Type CX/CB/CH) to print a ticket and to configure the unit. We offer special configuration software to completely configure the F119-P and read-out logged data, available on our website. Alternatively, the communication mode can be set to use the Modbus protocol via a serial connection.
  • Page 42 Page 42 Type CX: service port With type CX, a service port is available to configure the F119-P and read-out logged data via an external device, e.g. a laptop. The connection is not made with the standard type connectors, but the connections to terminals C1 through C4 are made via a special service port connector.
  • Page 43: Maintenance

    Page 43 5 MAINTENANCE GENERAL DIRECTIONS • Mounting, electrical installation, start-up and maintenance of this device may only be carried out by trained persons authorized by the operator of the facility. Persons must read and understand this manual before carrying out its instructions. •...
  • Page 44: Battery Replacement

    Page 44 BATTERY REPLACEMENT • Handle the battery with the utmost care to prevent a short circuit and damage. A mistreated battery can become unsafe. Unsafe batteries can cause (serious) injury to persons. Do not recharge, crush, disassemble, incinerate, heat above its rated temperature or expose the contents to water.
  • Page 45 Page 45 5.3.2 REPLACE THE CLOCK BACKUP BATTERY To remove the clock backup battery, follow these instructions: 1. Open the enclosure and remove the main battery as indicated in the previous section. 2. Remove all connectors. 3. Remove the two screws that fasten the plastic cover and then carefully remove the plastic cover.
  • Page 46: Technical Specification

    Page 46 TECHNICAL SPECIFICATION General Display Type High intensity reflective numeric and alphanumeric LCD, UV-resistant. Digits Seven 17mm (0.67") and eleven 8mm (0.31"). Various symbols and measuring units. Refresh rate User definable: 8 times/sec - 30 secs. Type ZB LCD with LED backlight. Improved readability in full sunlight and darkness. Enclosures General Die-cast aluminum, Stainless Steel or GRP (Glassfibre Reinforced Polyamide) enclosure with...
  • Page 47 Page 47 Reset total Type IB External reset totalizer input signal input Make-and-break contact - Additional functionality to lock the RESET button of the keyboard (as long as this contact is being made). Duration minimum 200 msec. to reset Total. Outputs Analog output Function...
  • Page 48: Problem Solving

    Page 48 PROBLEM SOLVING In this appendix, several problems are treated that can occur when the F119-P is going to be installed or while it is in operation. Flowmeter does not generate pulses: Check: • Signal selection; • Pulse amplitude; •...
  • Page 49: Modbus Communication

    Page 49 MODBUS COMMUNICATION General The product is fitted with the Modbus communication protocol and can be equipped with various physical interfaces like RS485 and RS232 (please see device datasheet for available options). The tables below show the various variables that can be accessed through the communication. Currently, the function codes supported are: •...
  • Page 50 Page 50 Runtime variables of the F119-P Reading flow rate, total, accumulated total or current day totals: When reading runtime variables, the given value may differ slightly from the value that is displayed on the display – this is due to the fact that the display is limited in the number of digits and may have a slower update rate.
  • Page 51 Page 51 Historical previous day totals of the F119-P – Integer based – Contiguous read The read-out of historical previous day totals is done via 2 INDEXED variables containing the number of decimals and the value. These 2 variables can be read as one contiguous list of 3 registers (in a single read action). Reading is done by first selecting the right entry (day) through the index.
  • Page 52 Page 52 [d] 2208 42209 Current day unit64 0.000…9999999999 [h] 0x8A0 total Representation: unit, decimals depending on variables 32, [d] 2216 42217 Previous uint64 0.000…9999999999 [h] 0x8A8 day total Representation: unit, decimals depending on variables 32, Flowrate VARIABLE TYPE VALUE / REMARKS HOLDING ADDRESS REGISTER...
  • Page 53 Page 53 Linearization The linearization table is an INDEXED variable. Reading and writing the entries of the linearization table is done by first selecting the entry through the index. Valid values for the index are 0…14, which correspond with the linearization table entries 1 through 15. Indexes outside this range will result in an error being sent back.
  • Page 54 Page 54 Modbus communication VARIABLE TYPE VALUE / REMARKS HOLDING ADDRESS REGISTER REGISTERS [d] 144 40145 speed uint16 0=1200 2=4800 4=9600HP 6=38400 [h] 0x090 (baudrate) 1=2400 3=9600 5=19200 7=57600 [d] 145 40146 modbus uint16 1…247 [h] 0x091 address [d] 146 40147 modbus uint16 0=off...
  • Page 55 Page 55 Others VARIABLE TYPE VALUE / REMARKS HOLDING ADDRESS REGISTER REGISTERS [d] 160 40161 model uint16 0…9999 [h] 0x0A0 number [d] 173 40174 model suffix char Representation: ASCII character [h] 0x0AD [d] 162 40163 firmware uint32 0…999999 [h] 0x0A2 version Representation: xx.xx.xx [d] 165...
  • Page 56: Declaration Of Conformity

    Page 56 DECLARATION OF CONFORMITY FW-F119-P-M_v2001_02_EN.docx...
  • Page 57: Index Of This Manual

    Page 57 INDEX OF THIS MANUAL actual settings measuring unit analog Flowrate cut-off value functional description disable/enable keys flowrate max. main-function flowrate min. maintenance tune / calibrate operational 9, 13, 29, 36, 43 clear total Operator level clear total password pass code communication power supply...
  • Page 58 Page 58 IST OF CONFIGURATION SETTINGS SETTING DEFAULT DATE: DATE: TOTAL Enter your settings here UNIT DECIMALS AUTO K-FACTOR FACTOR-X CLEAR PASSWORD CONTRACT HOUR 00:00 CURRENT DAY TOTAL ---- PREVIOUS DAY TOTAL ---- FLOWRATE UNIT TIME /min DECIMALS AUTO K-FACTOR CALCULATION PLS 10 30.0...
  • Page 59 TRANSMIT DELAY 15 ms LINE TERMINATION CR/LF START ROW END ROW FORM FEED disable DATE FORMAT YY.MM.DD TICKET 10.1 HEADER 1 FLUIDWELL 10.2 HEADER 2 <empty> 10.3 HEADER 3 <empty> 10.4 HEADER 4 <empty> 10.5 TICKET NR 10.6 AUTO PRINT disable 10.7...