• Input and Output terminals
The default setting of the input terminals is as follows:
- Terminal 9
- Terminal 8
- Terminal 7
- Terminal 6
- Terminal 5
- Terminal 4
- Terminal 12
The default configuration of the terminals dedicated to digital outputs are as follows:
- Terminal 56
- Terminal 57
- Terminal 54
- Terminal 55
- Terminal 52
- Terminal 53
- Terminal 50
- Terminal 51
Signals for the digital outputs can be programmed using the Digital output 1...4 src parameters (13 - DIGITAL OUT-
PUTS menu, PAR: from 1410 to 1416) using the settings in the L_DIGSEL1 selection list.
The drive also includes two analog outputs which are not factory-set. These outputs must be enabled by setting Ana-
log out 1X src (15 - ANALOG OUTPUTS menu, PAR: 1850) and Analog out 2X src parameters (PAR: 1852) with a
signal selected from selection list L_ANOUT.
The signal available on analog outputs is ± 10V.
The analog output signal can be adjusted using Analog out 1X scale (PAR: 1858) and Analog out 2X scale param-
eters (PAR:1860).
• Keypad
Use the LOC / REM key with the Enable input open (terminal 9 on terminal strip T2) to control running, to stop and re-
verse the direction of rotation of the motor using the operator keypad on the drive. Use the potentiometer or an analog
signal to control speed.
For information on how to use a digital speed reference, see the example on ADV100 Functions description and pa-
rameters list manual,
the direction of rotation of the motor.
When the Enable input is closed, to enable motor running press START. The motor starts the acceleration ramp and
moves to the speed set in the FWD direction. With the motor running you can adjust the speed using the Dig ramp ref
1 parameter (PAR: 600) and the acceleration/deceleration ramps using Acceleration time 0 (PAR: 700) and Decelera-
tion time 0 (PAR: 702).
To change the direction of rotation press FWD/REV.
To stop the motor with the deceleration ramp, press STOP.
If the Enable contact is opened the inverter bridge is immediately disabled and the motor stops for inertia
To return to control using the terminal strip commands and analog speed reference:
1.
Stop the motor
2.
Open the Enable terminal
3.
Press LOC / REM key.
Note !
For more customizations and any information that is not included in this initial customization guide, see the description of the parameters in this manual.
Digital input E
Enable
Digital input 1
FR forward src, PAR 1042
Digital input 2
FR reverse src, PAR 1044
Digital input 3
Multi ref sel 0 src
Digital input 4
Multi ref sel 1 src
Digital input 5
Fault reset src
+ 24V OUT
I/O supply
Relay 1 output
Drive OK (relè 1)
COM relay 1
Common relay 1
Relay 2 output
Drive ready (relè 2)
COM relay 2
Common relay 2
Relay 3 output
Ritardo velocità = 0
COM relay 3
Common relays 3/4
Relay 4 output
Ritardo riferim = 0
COM relay 4
Power supply relays 3/4
chapter
A.3 . The reference can have a positive or negative value, making it possible to reverse
ADV100 • Quick installation guide - Specifications and connection
65