Rated speed [rpm]:
Rated frequency [Hz]:
Pole pairs:
Rated power [kW]:
Rated power factor:
Note!
When data entry is complete the Take parameters command is executed automatically (menu 16 MOTOR DATA, PAR: 2020). The motor data entered during
the STARTUP WIZARD procedure are saved in a RAM memory to enable the drive to perform the necessary calculations.
These data are lost if the device is switched off. To save the motor data follow the procedure described in step 9.
At the end of the procedure proceed to step 3
Step 3 - Autotune of the motor
The drive carries out the motor autotune procedure (real measurement of motor parameters).
Autotune may last a few minutes.
Note !
If this operation generates an error message (example Error code 1), check the connections of the power and control circuits (see Step 1 - Connections),
check motor data settings (see Step 2 – Motor data setting) and then repeat the Autotune procedure (or, alternatively, select a different type of procedure
(Rotation or Still)
STARTUP WIZARD
Run autotune rot ?
E=Yes
(3A)
Step 3A - Self-tuning with rotating motor (Autotune rotation)
Use this procedure when the motor is not coupled or the transmission does not represent more than 5% of the load.
This procedure obtains the most accurate data.
Note !
Autotuning can be cancelled at any time by pressing
STARTUP WIZARD
Run autotune rot
E=Yes
Down=Next
Autotune
Progress:
Press ESC to abort
Note !
At the end of the self-tuning procedure there is a request to open the Enable contact (terminals 7 – S3); the Take tune parameters command (menu 16 MO-
TOR DATA, PAR: 2078) is automatically executed.
The calculated parameters are saved in a RAM memory to enable the drive to perform the necessary calculations. These data are lost if the device is
switched off. To save the motor data follow the procedure described in Step 6.
When the Enable contact is opened the drive proposes Step 4 to proceed with the wizard.
rated speed of the motor; this value must reflect the speed of the fully loaded motor at rated frequency. If slip is indicated on the motor data
plate, set the Rated speed parameter as follows: Rated speed = Synchronous speed - Slip (e.g. for a 4-pole motor Rated speed = 1500 - 70
= 1430).
rated frequency of the motor, as shown on the data plate.
Number of motor pole pairs. The number of motor pole pairs is calculated using the plate data and the following formula:
P = 60 [s] x f [Hz] / nN [rpm]
Where:
P = motor pole pairs, f = motor rated frequency (e.g. 50); nN = motor rated speed (e.g. 1450)
Motor rated power; for a motor data plate with an HP power value, set the rated power kW = 0.736 x the motor power HP value.
Leave the default rated power factor if the data are not available on the data plate.
STARTUP WIZARD
Run autotune still ?
Down=Next
E=Yes
(3B)
STARTUP WIZARD
E
Close Enable input
Esc=Abort
Autotune
5%
Done
ADV100 • Quick installation guide - Specifications and connection
Down=Next
Connect terminal 9 (Enable) to terminal 12
(+24Vdc). To interrupt this operation, press
the ESC key.
Autotune
Open Enable input
SEQ
SEQ. 01
PAR 2022
Autotune rotation
Press E to execute