BeaconMedaes dMED 7 Instruction Book page 53

Dual medical air purifiers
Table of Contents

Advertisement

Instruction book
(1)
Drying after service
(2)
Remaining time
• Dryer forced operation
The dryer forced operation function disables the automatic switch over and forces the system to keep on
working on the active dryer even though a pressure or dew point should occur. This function will be
disabled automatically after a preset time.
(1)
Drying forced operation
(2)
Remaining time
• Commissioning
To ensure the system is in good condition when it's being commissioned, this function can be used to
activate both dryers for a preset time. They will both operate according the predefined pressurization and
regeneration cycles with a fixed timing to obtain a reasonable dew point. This function has to be disabled
manually.
2920 7099 70
(3)
Activate
(3)
Modify
51