Parameter
Forced time
Remote to local
time
Start/load time
Unload time
Delta time
System Forced
function
Maximum power
down time
The following settings can be found under the ES Slave X submenu.
In normal circumstances they should not be changed, please contact BeaconMedæs.
Parameter
Scheme X priority To put this compressor in a certain
Start/load
reaction time
Stop reaction time To program the time interval in which the
Running hours
Mode
28
Function
To program the interval at which, if
activated by "System Forced", the central
controller starts a new compressor in
case no sequence change has occurred
during the interval
To program the time interval between
LAN and local commands from central to
compressor controllers
To program the time interval between the
different start commands from central to
compressor controllers
To program the time interval between
different stop commands from central to
compressor controllers
To program the difference in running
hours to allow the central controller to
decide starting another compressor
To allow the central controller to force
another sequencing by starting a new
compressor at the interval programmed
in "Forced Time"
If <ArAF> is set to <Active> (e.g. instead
of <Infinite>), then the system will only
restart automatically within this power
down time
Function
priority queue, based on the scheme
selected (see master parameter
"Scheme In Use" )
To program the time interval in which the
start command from the central controller
should result in the compressor running
stop command from the central controller
should result in stopping the compressor
To adjust running hours for compressor
X to influence the even wear control
algorithm
See below
Min.
Factory
setting
setting
1
1
5
20
2
20
2
20
10
168
2
2
15
20
Min.
Factory
setting
setting
1
1
1
20
1
35
0
X
-
integrated
Instruction book
Max.
Unit
setting
60
days
600
sec
600
sec
600
sec
672
sec
30
days
3600
sec
Max.
Unit
setting
6
-
600
sec
600
sec
500000
hrs.
-
-
2920 7099 70