3. Select the ENGINE PARAMETERS > FUEL LOW WARNING parameter.
4. Set the necessary percentage level with the up and down arrow key.
5. Press ENTER.
6. Select the ENGINE PARAMETERS > FUEL LOW SHUTDOWN parameter.
7. Set the necessary percentage level with the up and down arrow key.
8. Press ENTER.
9. Press NEXT to return to the main screen.
Set the parameters for the sump level transducer
1.
Go to OPERATION PARAMETERS > OPERATION MODE.
2.
Select the MANUAL/AUTO NO WARNING mode.
3.
Then, go to MAIN PARAMETERS > PUMP CONTROL PARAMETERS >
START/STOP TYPE.
4.
Select the LEVEL > START LEVEL parameter.
5.
To automatically start the pump, set the high level of sump with the up and
down arrow key.
6.
Press ENTER.
7.
Select the LEVEL > STOP LEVEL parameter.
8.
To automatically start the pump, set the low level of sump with the up and
down arrow key.
9.
Press ENTER.
10. Select the LEVEL > MAINTAIN LEVEL parameter.
11. Make sure that the maintain ft level is less than the stop level. Adjust as
necessary.
12. Go to MAIN PARAMETERS > ANALOG INPUT PARAMETERS.
13. Select the ANALOG INPUT 5 parameter.
14. Set the following values:
ZERO OFFSET
MAX
Sump level transducers are typically rated in psi, which is displayed on the
transducer. The psi rating of the sump level transducer must be converted
to feet.
Example: 15 psi transducer x 2.31 = 35 feet.
15. Press NEXT to return to the main screen.
16. Set the key to OFF to set parameters in the controller memory.
FST Installation, Operation, and Maintenance Manual
Value
4.00 mA
Maximum value of the level transducer in ft.