Chapter 7 - Troubleshooting
If the MCCID is zero (in format MCC Helper v1.16a (0) from 4F.91.E6.20.92.1F
[FE.FF.00.A7]), a CPU configuration failure occurred and the DCW was unable to
communicate with the CPU. To configure the CPU so it can communicate with the DCW, complete
the following steps:
1. Connect to the CPU using Hyperterm, and then select Y in the Boot screen to boot the unit into
diagnostic mode.
2. Type C.
The EEPROM Configuration menu is displayed for you to verify information.
3. Verify or edit the programmed values for:
•
•
•
•
•
•
•
•
Follow the instructions and exit the EPROM menu, booting only if requested by the unit.
78
MccNetAddress
MccNodeAddress
LogMgrNetAdddress
LogMgrNodeAddress
AlarmNetAddress
AlarmNodeAddress
MinutesFromGMT
DayLightSavingsType
98-1031 Rev AA
Series IV Concentrator U and I Guide