Chapter 6 - Performing System Upgrades
Switch
-disconnect
-nohotboot
-waittime
-bankcopy
-debugprint
-help
-query
-switchover
Switchover Concentrator
After the download is complete, login to the concentrator to instruct it to switchover.
1. Open a command window on your PC.
2. Use your administrative credentials to login as control user.
3. Type
./utlICDownload -mccad 30000.1 -session 2 -switchover
58
Table 6-1. Download Command Line Switches (continued)
Description
You need the disconnect session ID if the earlier download
was terminated before completion. In this case, you must
enter all the options of the download command and include
the disconnect session ID. That should be the same session
number that was terminated earlier.
Example: utlICDownload -disconnect 5
Override automatic disconnect and hotboot to avoid hot
booting the MC be fore the session. In this case, you must
start run disconnect and hotboot.
Example: utlICDownload -nohotboot -session 5 -mccad
30000.1 -s <filename>
Time to wait (in seconds) before sending the next packet. The
download firmware process sends a total of nine packets. The
waittime option allows for a delay between packets sent.
Example: utlICDownload -waittime 4
/MCCCTR/image.bin
Copy Concentrator image from B to A. The Concentrator must
be running the image from B.
This option applies to versions 14.02.06 and greater.
Example: utlICDownload -mccad 30000.1 -bankcopy
Dump raw hex.
Example: utlICDownload -debugprint
Print help information.
Example: utlICDownload -help
Get status of concentrator.
Example: utlICDownload -query
Switchover concentrator.
Example: utlICDownload -switchover
The concentrator hot boots after this step.
98-1031 Rev AA
[Args Reqd: 1 defaults: 2
[Args Reqd: 1 defaults: 2
Concentrator User and Installation Guide
Landis+Gyr
format: %s]
format: %s]