The Parameter Of System - Pylontech PowerCube-M1 Product Manual

Lithium-ion phosphate battery
Hide thumbs Also See for PowerCube-M1:
Table of Contents

Advertisement

2.2.1 The parameter of system

No.
1
Cell Technology
2
Battery System Capacity (kWh)
3
Battery System Voltage (V
4
Battery System Capacity (Ah)
5
Battery Controller Name
6
Battery Module Name
7
Battery Module Quantity (pcs)
8
Battery Module Capacity (kWh)
9
Battery Module Voltage (V
10
Battery Module Capacity (Ah)
11
Battery Module Cell Quantity (pcs)
12
Battery System Charge Voltage (V
13
Battery System Charge Current (Standard)
14
Battery System Charge Current (Normal)
15
Battery System Charge Current (Max.)
16
Battery System Discharge lower-Voltage (V
17
Battery System Discharge Current (Standard)
18
Battery System Discharge Current (Normal)
19
Battery System Discharge Current (Max.)
20
Efficiency
21
Depth of Discharge
22
Dimension (W*D*H, mm)
23
Communication
24
Protection Class
25
Weight (kg)
26
Operation Life (Years)
27
Operation Cycle Life
28
Operation Temperature (℃)
29
Storage Temperature (℃)
30
Humidity
31
Altitude (m)
32
Product Certificate
33
Transfer Certificate
34
Pollution Degree (PD)
Other:
1)Battery Controller Dimensions (W*D*H)
35
2)Battery Module Dimensions (W*D*H)
Remark: The parameter will be changed when the battery modules in different series (1~23 pcs
battery modules).
Item
)
dc
)
dc
)
dc
)
dc
6 / 15
POWERCUBE-M1
(736V148AH)
Li-ion (LFP)
108.9
736
148
SC1000-200
H32148
23
4.74
32
148
10
828.0
29.6
74
148
690.0
29.6
74
148
96%
80% (10~90%)
815*659*2130
RS485\CAN
IP20
1250
10
3500
10~40
-20~60
5%~95%
<2000
TÜV, CE
UN38.3
II
330*628*150.5
330*628*150.5
18 PIMP0801

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents