Compressor Timers - Danfoss AK-PC 772A User Manual

Capacity controller for adap-kool small co2 refrigeration system
Table of Contents

Advertisement

Two independent speed-regulated compressors
If the two speed-regulated compressors need to be controlled
asynchronously, they must each have their own analogue voltage
signal.
The controller first starts one of the speed-regulated compressors.
If more capacity is required, the other speed-regulated compres-
sor is started, and then the single compressors.
Analogue outputs
Max. speed
Nominal
Start speed
Min. speed
The first is run up to maximum speed. Number two is then acti-
vated and run up to nominal speed – and kept there. The speed
of number one is reduced at the same time, so the capacity is ba-
lanced. All variations are now handled by number one. If number
one reaches maximum speed, number two will also be raised.
If number one reaches minimum speed, it will be kept there while
number two takes over the variation below its nominal speed.
When engaging and disengaging, the total hours of operation for
the compressors is compared, so they are run an equal number of
hours.
AK-PC 772A
Capacity controller RS8HF102 © Danfoss 2017-07

Compressor timers

Time delays for cutins and cutouts
To protect the compressor against frequent restarts three time
delays can be put in.
- A minimum time to run from a compressor's startup and until it
may be restarted.
- A minimum time (ON-time) for the compressor to operate before
it may be stopped again.
- A minimum OFF time to run from a compressor stops and until it
may be restarted
When unloaders are cut in and out, the time delays will not be
used.
Timer
The operating time of a compressor motor is registered continu-
ously. You can read out:
- operating time for the previous 24-hour period
- total operating time since the timer was last set to zero-set.
Equalizing operating hours
Operating hours are also summed in the "Equalization time" field.
During cyclical operation, this field is used for equalizing opera-
ting hours.
Coupling counter
The number of relay cutins and cutouts is registered continuously.
The number of starts can be read out here:
- Number during the previous 24-hour period
- Total number since the counter was last set to zero-set.
95