Check Configuration - Danfoss AK-PC 772A User Manual

Capacity controller for adap-kool small co2 refrigeration system
Table of Contents

Advertisement

Configuration - continued

Check configuration

1. Go to Configuration menu
2. Select I/O configuration
3. Check configuration of Digital Outputs
Press the +-button to go on to the next page
4. Check configuration of Digital Inputs
76
This control requires that the setup is locked
(Only when the setup is locked are all settings for in- and out-
puts activated.)
The setup of the digital
outputs appears as it is sup-
posed to according to the
wiring made.
The setup of the digital
inputs appears as it is sup-
posed to according to the
wiring made.
Capacity controller RS8HF102 © Danfoss 2017-07
An error has occurred, if you see the fol-
lowing:
A 0 – 0 next to a defined function.
If a setting has reverted to 0-0, you must control
the setup again.
This may be due to the following:
• A selection has been made of a combination of
module number and point number that does
not exist.
• The selected point number on the selected mod-
ule had been set up for something different.
The error is corrected by setting up the output
correctly.
Remember that the setup must be unlocked be-
fore you can change module and point numbers..
The settings are shown on a RED background.
If a setting has turned red, you must control the
setup again.
This may be due to the following:
• The input or the output has been set up; but the
setup has later been changed so that it should
no longer be applied.
The problem is corrected by setting module
number to 0 and point number to 0.
Remember that the setup must be unlocked be-
fore you can change module and point numbers.
AK-PC 772A

Advertisement

Table of Contents
loading

Table of Contents