Wiring - Danfoss AK-PC 772A User Manual

Capacity controller for adap-kool small co2 refrigeration system
Table of Contents

Advertisement

Mounting and wiring - continued

Wiring

Decide during planning which function is to be connected and
where this will be.
1. Connect inputs and outputs
Here are the tables for the example:
Signal
Module
Shr container temperature
Suction gas temperature - Ss MT
Discharge temperature - Sd MT
Suction pressure - P0 MT
Condensing pressure - Pc MT
Suction gas temperature - Ss LT
Discharge temperature - Sd LT
Suction pressure - P0 LT
Compressor 1 MT
Compressor 2 MT
Compressor 3 MT
Compressor 1 LT
Compressor 2 LT
Valve and circulation pump HR
Fan motors
Hot gas dump
Signal
Module
Compressor 1 MT Gen. Safety
Compressor 2 MT Gen. Safety
Compressor 3 MT Gen. Safety
All compressors common safety
MT
Compressor 1 LT Gen. Safety
Compressor 2 LT Gen. Safety
All compressors common safety LT
2
Stepper signal to by-pass valve,
CCM
Stepper signal to high pressure
valve, CCMT
Signal
Module
Outdoor temperature Sc3
Temp. gas cooler outlet Sgc
Gas cooler pressure Pgc
Receiver pressure Prec
3
Speed control, compressor MT
Speed control, compressor LT
Speed control, compressor, EC
46
Point
Signal type /
Terminal
1 (AI 1)
1 - 2
2 (AI 2)
3 - 4
Pt 1000
3 (AI 3)
5 - 6
4 (AI 4)
7 - 8
Pt 1000
5 (AI 5)
9 - 10
Pt 1000
6 (AI 6)
11 - 12
AKS 2050-59
7 (AI 7)
13 - 14
AKS 2050-159
8 (AI 8)
19 - 20
9 (AI 9)
21 - 22
Pt 1000
10 (AI 10)
23 - 24
Pt 1000
11 (AI 11)
25 - 26
AKS 2050-59
1
12 (DO 1)
31 - 32
ON
13 (DO 2)
33 - 34
ON
14 (DO 3)
35 - 36
ON
15 (DO 4)
37 - 38
ON
16 (DO 5)
39 - 40 - 41
ON
17 (DO6)
42 - 43 - 44
ON
18 (DO7)
45 - 46 - 47
ON
19 (DO8)
48 - 49 - 50
ON
24
-
25
-
Point/Step
Terminal
Signal type
1 (AI 1)
1 - 2
Open
2 (AI 2)
3 - 4
Open
3 (AI 3)
5 - 6
Open
4 (AI 4)
7 - 8
Open
5 (AI 5)
9 - 10
Open
6 (AI 6)
11 - 12
Open
7 (AI 7)
13 - 14
Open
8 (AI 8)
15 - 16
9 (step 1)
25 - 26 - 27 - 28 CCM (ETS)
10 (step 2)
29 - 30 - 31 - 32
11 (step 3)
33 - 34 - 35 - 36 CCMT
12 (step 4)
37 - 38 - 39 - 40
Point
Terminal
Signal type
1 (AI 1)
1 - 2
Pt 1000
2 (AI 2)
3 - 4
Pt 1000
3 (AI 3)
5 - 6
AKS 2050-159
4 (AI 4)
7 - 8
AKS 2050-159
5 (AO 1)
9 - 10
0 - 10 V
6 (AO 2)
11 - 12
0 - 10 V
7 (AO 3)
13 - 14
0 - 10 V
8 (AO 4)
15 - 16
Capacity controller RS8HF102 © Danfoss 2017-07
Remember the isolation amplifier
If signals are received from different controls, e.g. heat re-
covery for one of the inputs, a galvanically insulated module
should be inserted.
Active at
The function of the switch functions can be seen in the last column.
There are pressure transmitters AKS 32R and AKS 2050 available for
several pressure ranges.
Here there are two different ones. One up to 59 bar and two up to 159
bar.
AK-PC 772A