Danfoss AK-PC 772A User Manual page 113

Capacity controller for adap-kool small co2 refrigeration system
Table of Contents

Advertisement

Display of suction pressure and condensing pressure
One to four separate displays can be connected to the controller.
Connection is accomplished by means of wires with plug
connections. The display may be placed in a control box front, for
example.
When a display is connected, it will show the value for what is indi-
cated in the setup. It can be:
Suction control Temperature
T0-MT
P0-MT pressure
T0-LT
P0-LT pressure
Ss-MT
Sd-MT
Ss-LT
Sd-LT
Cond. control sensor
Tc-MT
Pc-MT pressure
Sgc
Pgc
Prec
MT Speed compressor
LT Speed compressor
When (on plug A) a display with control buttons is chosen, a sim-
ple operation via a menu system can be performed in addition to
the display of suction pressure and condensing pressure:
No.
Function
o57
Capacity settings for condenser
0: MAN, 1: OFF, 2: AUTO
058
Manual setting of condenser capacity
o59
MT Capacity setting for suction group
0: MAN, 1: OFF, 2: AUTO
o60
MT Manual setting of suction capacity
o93
Lock of configuration
It is only possible to select a predefined configuration or change refrigerant when the
configuration lock is open.
0 = Configuration open
1 = Configuration locked
P62
LT Manual setting of suction capacity
P63
LT Capacity setting for suction group
0: MAN, 1: OFF, 2: AUTO
r23
MT Set point suction pressure
Setting of required suction pressure reference in °C
r24
MT Suction pressure reference
Actual reference temperature for compressor capacity
r12
Main switch
0: Controller stopped
1: Regulating
r28
Set point condenser
Setting of required condenser pressure in °C
r29
Condenser reference
Actual reference for temperature for condenser capacity
r57
MT To evaporating pressure in °C
r90
LT To evaporating pressure in °C
r91
LT Suction pressure reference
r92
LT Set point suction pressure
u21
MT Superheat in suction line
u44
Sc3 out door temperature in °C
AK-PC 772A
Capacity controller RS8HF102 © Danfoss 2017-07
u48
Actual regulation status on condenser
0: Power up
1: Stopped
2: Manuel
3: Alarm
4: Restart
5: Standby
6: Unloaded
7-9: Part loaded
10: Full loaded
11: Running
u49
Cut in condenser capacity in %
u50
Reference for condenser capacity in %
u51
MT Actual regulation status on suction group
Actual regulation status on suction group MT circuit
0: Standby
1: Normal control
2: Compressor alarm
3: ON timer active
4: OFF timer active
5: Normal control
6: Injection ON delay
7: Coordination
8: Compressor 1 delay active
9: Pump down
10: Sensor error
11: Load shed is active
12: High Sd
13: High Pc
14: Manual control
15: OFF
u52
MT Cut in compressor capacity in %
u53
MT Reference for compressor capacity
u54
MT Sd discharge gas temperature in °C
u55
MT Ss Suction gas temperature in °C
U01
MT Actual Pc condensing pressure in °C
U46
LT Reference for compressor capacity
U47
LT Cut in compressor capacity in %
U48
LT Actual regulation status on suction group (see value in u51)
U49
LT Actual Pc condensing pressure in °C
U50
LT Ss Suction gas temperature in °C
U51
LT Sd discharge gas temperature in °C
U52
LT Superheat in suction line
AL1
Alarm suction pressure
AL2
Alarm condenser
- - 1
Initiation, Display is connected to output "A", (- - 2 = output "B" etc.)
If you want to see one of the values for what is given under "func-
tion" you should use the buttons in the following way:
1. Press on the upper button until a parameter is shown
2.Press on the upper or lower button and find the parameter you
want to read
3. Press on the middle button until the value of the parameter is
displayed.
After a short time, the display will return automatically to the
"Read out display".