Separate Thermostat; Separate Pressostat - Danfoss AK-PC 772A User Manual

Capacity controller for adap-kool small co2 refrigeration system
Table of Contents

Advertisement

Configuration - continued

Separate thermostat

1. Select thermostat
2. Select actual thermostat
3. Define the required thermostat
functions

Separate pressostat

1. Select pressostat
2. Select actual pressostat
3. Define the required pressostat
functions
68
In our example, separate
thermostat functions are not
used.
In our example, separate
pressostat functions are not used.
Capacity controller RS8HF102 © Danfoss 2017-07
3 - Thermostats
The general thermostat can be used to monitor a tempera-
ture. The thermostat has a separate outlet to control external
automation.
Settings
• Whether the thermostat should also be shown in overview
display 1.
(The function is always shown in overview display 2)
• Name
• Which of the sensors is used
Actual temp.
Temperature measurement on the sensor that is attached to
the thermostat
Actual state
Actual status on the thermostat outlet
Cut out temp.
Cut-out value for the thermostat
Cut in temp.
Cut-in value for the thermostat
High alarm limit
High alarm limit
Alarm delay high
Time delay for high alarm
Alarm text high
Indicate alarm text for the high alarm
Low alarm limit
Low alarm limit
Alarm delay low
Time delay for low alarm
Alarm text low
Indicate alarm text for low alarm
3 - Pressostat
Settings as the thermostat
AK-PC 772A

Advertisement

Table of Contents
loading

Table of Contents