6 Related Parameters

6
Related Parameters
The following parameters are used to set up the drive for operation with the option.
Confirm proper setting of parameters in
No.
Name
(Addr. Hex)
b1-01
Frequency Reference
(180)
Selection
<1>
b1-02
Run Command
(181)
Selection
<1>
Operation Selection
F6-01
after
(3A2)
Communications
Error
External Fault
F6-02
Detection Conditions
(3A3)
(EF0)
Stopping Method for
F6-03
External Fault from
(3A4)
Communication
Option
F6-07
NetRef/ComRef
(3A8)
Selection Function
Reset
F6-08
Communication
(36A)
Related Parameters
F6-40
(3D5)
MAC ID
<3>
28
Table 9
Table 9 Related Parameters
Selects the frequency reference input source
0: Operator - Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS/Modbus communications
3: Option PCB
4: Pulse Input (Terminal RP)
Selects the run command input source
0: Digital Operator - RUN and STOP keys
1: Digital input terminals S
2: MEMOBUS/Modbus communications
3: Option PCB
Determines drive response when a bUS error is detected
during communications with the option
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
<2>
Sets the condition for external fault detection (EF0)
0: Always detected
1: Detected only during operation
Determines drive response for external fault input (EF0)
detection during CompoNet communication
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
<2>
0: Multi-step speed reference disabled
1: Multi-step speed reference allowed
Determines which F6-
reset to default values when the drive is initialized using
A1-03.
0: Do not reset parameters
1: Reset parameters
Selects the drive MAC address
Note: Used in the CompoNet Link Object
YASKAWA ELECTRIC TOBP C730600 54A V1000 Option CompoNet Installation Manual
before starting network communications.
Description
and F7-
parameters are
Values
Default: 1
Range: 0 to 4
(Set to 3 for
CompoNet only)
Default: 1
Range: 0 to 3
(Set to 3 for
CompoNet only)
Default: 1
Range: 0 to 3
Default: 0
Range: 0, 1
Default: 1
Range: 0 to 3
Default: 1
Range: 0, 1
Default: 0
Range: 0, 1
Default: 0
Min: 0
Max: 63