5 Installation Procedure
4.
On IP20/Open-Chassis models, connect the drive-side of the ground wire to the
drive ground terminal.
Note: The four different ground wires packaged with the option connect the option to different drive
models. Select the proper ground wire depending on drive size.
Figure 7
Figure 7 Connect the Ground Wire on an IP20/Open-Chassis Drive
5.
For IP20/Open-Chassis models, go to Step
6.
For IP20/NEMA Type 1 Enclosure models CIMR-V
on the front of the NEMA Type 1 terminal cover and remove it from the drive. Refer
to
Figure 8
Refer to
Figure 9
2A0069F, and 4A0001F to 4A0038F, which require removing the plastic terminal
cover prior to removing NEMA Type 1 terminal cover.
Note: Installing the option on an IP20/NEMA Type 1 enclosure drive voids NEMA Type 1 protection
while maintaining IP20 conformity.
Figure 8
20
Ground terminal
Ground wire
for details
for drive models CIMR-V BA0006F to BA0018F, 2A0008F to
Figure 8 Remove the NEMA Type 1 Terminal Cover
YASKAWA ELECTRIC TOBP C730600 54A V1000 Option CompoNet Installation Manual
Option unit
connector
Screw size: M3
Ground wire
9.
on page 23.
Drive-side
connector
Screw size:
M3.5 to M6
A
F, loosen the screw