Fault messages generated by the drive

Code Fault
OVERCURRENT
0001
0002
DC
OVERVOLTAGE
0003
DEVICE
OVERTEMP
SHORT CIRCUIT
0004
DC
0005
UNDERVOLTAGE
Cause
Output current has
exceeded the internal fault
limit.
Excessive intermediate
circuit DC voltage.
Measured drive
temperature has exceeded
the internal fault limit.
Short-circuit in the motor
cable(s) or motor.
Intermediate circuit DC
voltage is not sufficient due
to missing mains phase,
blown fuse or rectifier
bridge internal fault.
Fault tracing 299
What to do
Check motor load.
Check acceleration time. See
parameter group
25 ACC/DEC
RAMP
on page 236.
Check the motor and motor cable
(including phasing and delta/star
connection).
Check that the start-up data in
parameter group
99 START-UP
DATA
corresponds to the motor
rating plate.
Check that there are no power
factor correction capacitors or
surge absorbers in the motor cable.
Check the encoder cable (including
phasing).
Check the mains for static or
transient overvoltage.
Check the brake chopper and
resistor (if used).
Check the deceleration time.
Use the coast-to-stop function (if
applicable).
Retrofit the frequency converter
with the brake chopper and brake
resistor.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-
up.
Check motor power against unit
power.
Check the motor and motor cable.
Check that there are no power
factor correction capacitors or
surge absorbers in the motor cable.
Check mains supply and fuses.