Control Unit - Swegon GOLD RX Series Instructions For Installation Manual

Sizes 100/120
Table of Contents

Advertisement

3. Wiring terminals, control unit
1
2
3
4
5
6
7
A
B
GND
+
-
+
-
Com 1
Com 2
Com 3
Sensor 1 Sensor 2
Digital inputs, terminals 4-17, are of extra-low voltage type. Analogue inputs, terminals 18-19 have an input impedance of 66 kΩ.
Wiring
Function
terminal
1,2,3
Connections for EIA -485
4,5
External stop
6,7
External fire/smoke function 1
8,9
External fire/smoke function 2
10,11
External alarm 1
12,13
External alarm 2
14,15
External low speed
16,17
External high speed
18,19
Demand control
20,21
Circulation pump, heating circuit
22,23
Circulation pump, cooling circuit or
cooling on/off, 1-step operation
24,25
Cooling, on/off, 2-step operation
26,27
In-service indication
28,29,30
Damper control
31,32
Control voltage
1)
33,34
Reference voltage
35,36,37,38 Control, recirculation damper
The max permissible common load on terminals 31-32, outputs for Heat/Cool and damper output (terminals 28-30) is 50 VA.
1)
GOLD 100/120: If more than 16 VA is required, use wiring terminals 201 (G) and 202 (G0). Terminals 201-202 can be loaded
with a total of max. 48 VA.
Swegon reserves the right to alter specifications.
8
9
10
11
12
13
14
15
16
+
-
+
-
+
-
+
-
+
Com 4
Com 5
SA Temp
Sensor 3
Sensor 4
Remarks
1= Communication connection A/RT+, 2= Communication connection B/RT–, 3= GND/COM.
Stops the air handling unit by opening the circuit. On delivery, this function is fitted with a jumper. If
the connection is interrupted, the air handling unit will stop.
External fire and smoke function. On delivery, this function is fitted with a jumper. If the connection is
interrupted, the function will trip and initiate an alarm.
External fire and smoke function. On delivery, this function is fitted with a jumper. If the connection is
interrupted, the function will trip and initiate an alarm.
External contact function. Optional: Normally open/normally closed.
External contact function. Optional: Normally open/normally closed.
External contact function. Overrides the time switch from stop to low speed operation.
External contact function. Overrides the time switch from stop or low speed to high speed operation.
Input for 0-10 VDC. The input signal influences the supply air/extract airflow setpoint if the unit is
operating in the demand control mode. For connection of a sensor, for example CO
Independent contact, max. 5 A/AC1, 2 A/AC3, 250 VAC. Closes on a heating load.
Independent contact, max. 5 A/AC1, 2 A/AC3, 250 VAC. Closes on a cooling load.
Independent contact, max. 5 A/AC1, 2 A/AC3, 250 VAC. Closes on a cooling load.
Independent contact, max. 5 A/AC1, 2 A/AC3, 250 VAC. Closes when the unit is operating.
24 VAC. 28= Controlled 24 VAC (G), 29= 24 VAC (G), 30= 24 VAC (G0).
24 VAC control voltage. Terminals 31-32 are loaded with a total of 16 VA. Opened by means of the
safety isolating switch.
Output for constant 10 VDC. Max. permissible load: 8 mA.
The recirculation damper can be loaded with max. 2 mA at 10 VDC. 35= 24 V AC (G), 36= 24 V AC (G0),
37= 0-10 V DC control signal, 38= 0-10 VDC feedback signal.
The max. permissible load on the
corresponding connection is 16 VA.
17
18
19
20
21
22
-
+
-
C
NO
C
Heat
Cool
SD
Com 6
Com 7
Com 8
Com 9
+
-
G
G0
Y
U
33
34
35
36
37
38
GB.GOLDINE120.130915
23
24
25
26
27
28
29
NO
C
NO
C
NO
P
G
WLAN
CPU 2
CPU 1
Com 10 Com 11
24V AC In
18V AC In
230V AC Out
230V AC In
39 40
41 42
43 44
45 46
2
www.swegon.com
30
31
32
G0
G
G0
24V AC
47
, CO and VOC
31

Advertisement