1.11 Duct connection

The air handling unit's connection frames are rectangular
and can be jointed to ducts by means of slip-clamps.
The ducts should be insulated according to local regula-
tions and customary trade standards.
Swegon reserves the right to alter specifications.

1.12 To install the supply air sensor

The supply air temp. sensor must be mounted inside the
supply air duct.
The sensor must be positioned at a spot that is at least 1.5
metres from the air handling unit.
NOTE! If an air heater and/or air cooler, if required, is
installed in the system, the sensor must be positioned 1.5
metres from the unit measured from this component.
1. Measure and mark where the sensor is to be placed.
2. Drill an 11 mm dia. hole in the supply air duct.
3. Apply sealing compound around the hole and secure
the sensor by means of 2 self-tapping screws.
4. Connect the sensor's quick-fit connector to the appro-
priate socket on the control circuit board of the air
handling unit. See Section 1.15.
GB.GOLDINE120.130915
A
B
A
B
A >= 1500 mm
B
= 10000 mm
C
= Ø 11 mm
C
www.swegon.com