Lighting Control; Start-Up And Zero Point Calibration - Swegon ADAPT Parasol b Technical Manual

Table of Contents

Advertisement

ADAPT Parasol b
Control of the lighting
Use of analogue output to switch an external relay
The regulator's analogue outputs no. 13 or 19 (see page
16) can be used to switch an external relay for lighting.
The output is really intended to control actuators or
internal dampers, but when 10V is fed on the output for
occupancy (assuming that the output is configured 2-step,
i.e. 0% output signal for unoccupied and 100% output
for occupancy) lighting can also be managed for example
by means of an external relay.
Note that this is an alternative use of the output, which
means no intelligence for lighting control is connected to
this.
For more information and assistance with connections
contact the factory.
Swegon reserves the right to alter specifications.
Start-up and Zero point cali-
bration
During initial start-up after a power failure and for zero
point calibration, the internal damper will open to fully
open to read the current duct pressure in this position.
The damper is open for a few minutes and then closes
and then start normal regulation of the airflow.
For zero point calibration, close the damper, the pressure
sensor actual value is reset and then the start-up proce-
dure is performed as above.
Calibration is activated via SuperWISE, SWICCT or via
Modbus.
25/11/2014