9. Connect the grounding wire, if required, to the pole ground or neutral ground as local code
allows. If no ground wire is present, install a 8' by 5/8" copper clad steel ground rod and connect
with the proper clamp. Attach the ground wire to the pole with the proper staples and standard
spacing.
A. Be sure to avoid right angle or sharp bends in routing the ground wire.
B. Bond this ground wire to the power neutral if local rules require.
10. Energize the Extender by moving the power disconnect to the ON (closed) position in the
installed power disconnect box.