Set Up An Alarm Source In I-Vu Ccn Pro; To Set Up, Edit, Or Disable Alarm Sources - Carrier i-Vu CCN Pro 4.2 Installation Manual

Table of Contents

Advertisement

Field
Text to write to the file
Write as Report
Run Conditions

Set up an alarm source in i-Vu CCN Pro

In i-Vu CCN Pro you can:
Edit an alarm source's settings or set up a new alarm source to generate alarms
Select Properties page > Alarm Sources tab to set up all alarms associated with a particular piece of
equipment

To set up, edit, or disable alarm sources

To set up, edit, or disable a single alarm source:
On the navigation tree, select the alarm source.
1
Click Alarms, then select the Enable/Disable tab.
2
i-Vu CCN Pro 4.2
Notes
Use punctuation, spaces, or returns after the entries to format the text.
To add live data to the text, select field codes from the
Select to write a i-Vu CCN Pro report to a file, then select the Report and the
Format.
NOTE The Report Name field shows a custom report only if it was created at the
current system level.
Run as shows the name and login name of the operator creating the alarm action.
The report will be run using the privileges and report options of this operator.
TIP You may want to create a new operator with limited privileges for this purpose.
By default, i-Vu CCN Pro performs an alarm action when the alarm source
generates an alarm and when it returns to normal. Under Perform Action you can
choose to:
Run the alarm action only when the alarm source generates an alarm or when
it returns to normal.
Wait for the specified amount of time, then run the alarm action if the alarm
has not been acknowledged or has not returned to normal. *
Run if the alarm occurs during the occupied hours defined for a schedule
group or run if the alarm occurs during the unoccupied hours defined for a
schedule group. *
EXAMPLE: To have i-Vu CCN Pro perform one alarm action during work hours
and a different alarm action after work hours:
1. Create a schedule group (page 49), but do not assign members to it.
2. Create a schedule for the group. Set the occupied hours to be the same as
the work hours.
3. Create the alarm action that you want i-Vu CCN Pro to perform during work
hours. Under Run Conditions, select Run if schedule group <your new
group> is Occupied.
Create the alarm action that you want i-Vu CCN Pro to perform during after hours.
Under Run Conditions, select Run if schedule group <your new group> is
Unoccupied.
Monitor and control equipment
list.
Append Field Code