To perform downloads from a Properties page or a microblock pop-up

Downloading from a Properties page downloads memory, parameters, and schedules for the selected
equipment.
Go to a Properties page or microblock pop-up for the equipment.
1
Click the Download button below the red download message at the top of the page.
2
NOTE The Download button is visible only if a download is required.

If an item fails to download

All items that fail to download appear in the Failures list on the Download page. To attempt the download
again:
Select the item from the Failures list.
1
Review the reason for the failure at the bottom of the page.
2
Correct the problem.
3
Click Add to add the failed item to the Download Items list.
4
Click OK.
5
Select the item(s) in the Download Items list.
6
Click Download Selected Items.
7

To resolve a mismatch

A mismatch occurs when a value in a controller does not match the value in i-Vu CCN Pro Server. You can use
either of the following methods to handle mismatches in your system.
A. Select Always upload properties from controllers to i-Vu CCN Pro Server on mismatch on the
Communications tab of the System Settings page to have i-Vu CCN Pro upload automatically.
B. Clear Always upload properties from controllers to i-Vu CCN Pro Server on mismatch so that you can
evaluate every mismatch to determine the correct value.
If you use method B and a mismatch occurs:
Go to the Properties page for the equipment.
1
Click Details at the top of the page.
2
Do one of the following:
3
Click Upload to upload parameters from the controller to i-Vu CCN Pro Server.
Click Download to download parameters from i-Vu CCN Pro Server to the controller.

Setpoints

Use setpoints to set temperature values that control the HVAC equipment. i-Vu CCN Pro displays green when
a zone is within the desired temperature range determined by the heating and cooling setpoints.
Programmed setpoints are set and changed by operators.
i-Vu CCN Pro 4.2
Operating i-Vu CCN Pro
33