Manage Setpoints - Carrier i-Vu CCN Pro 4.2 Installation Manual

Table of Contents

Advertisement

Monitor and control equipment

Manage setpoints

The Setpoint area, as shown on a standard equipment graphic, indicates the base setpoint values (Occupied
High/Low, Unoccupied High/Low). i-Vu CCN Pro reads these values back periodically, typically within 10
seconds. The timing can vary based on bus traffic, the number of controllers in the database, and several
other variables. Setpoints that are changed in the field via another user interface (Network Service Tool,
ComfortVIEW, etc.) are displayed in i-Vu CCN Pro as soon as they are detected.
You can, at any time, change the setpoints from i-Vu CCN Pro graphics by using the slider or by entering
numeric values directly. Updated setpoints are transmitted to the controller when you Accept the changes.
Setpoints can also be changed via the setpoint tables that are discovered when a controller is scanned.
The various color bars are used to indicate adherence to or deviation from the setpoint. You can change the
current default settings for setpoint deviation.
Color
44
Condition
Green
Temperature is within the Occupied Low and High Setpoint
Grey
Temperature is within the Unoccupied Low and High Setpoint
Light Blue
Temperature is less than 2°F below the Occupied Low
Setpoint
Dark Blue
Temperature is more than 2°F below the effective Low Setpoint
but less than 4°F below the effective Low Setpoint
Yellow
Temperature is less than 2°F above the effective High
Setpoint
Orange
Temperature is more than 2°F above the effective High
Setpoint but less than 4°F above the effective High Setpoint
Red
Temperature is more than 4°F above or below the effective
setpoints
i-Vu CCN Pro 4.2