[7] User connection
User connection is used to connect a client to the lower devices via LAN port.
Item
(a)
Protocol
(b)
Specify connection use
(c)
Communication method
(d)
Open method
(Server / Client)
(e)
Open method
(Automatically / Manually)
(f)
Port No.
Description
Set communication protocol.
<Initial> MEWTOCOL-COM
<Set range> MEWTOCOL-COM / MEWTOCOL7-COM /
MODBUS TCP / MEWTOCOL-DAT /
General communication *1
Select use the connection or not.
<Initial> without check = not available
Set communication method.
<Initial> TCP/IP
<Set range> TCP/IP / UDP/IP
Set connection open method.
<Initial> Server connection (Any destination)
<Set range> Server connection (Any destination) /
Server connection (Specified) / Client connection
Set connection open method.
<Initial> Automatically
<Set range> Automatically / Manually
Set port number to use by ELC500.
<Initial> connection 1: 60001
connection 3: 60003
connection 5: 60005
connection 7: 60007
connection 9: 60009
connection 11: 60011
connection 13: 60013
connection 15: 60015
<Set range> Open method (Client): 0 to 65535
Open method (Server): 1 to 65535
59
ELC500 Control unit
(a)
(b)
(c)
(d)
(e)
(f)
(g)
(h)
(i)
connection 2: 60002
connection 4: 60004
connection 6: 60006
connection 8: 60008
connection 10: 60010
connection 12: 60012
connection 14: 60014
connection 16: 60016