3.2.4

Wiring of COM Port Terminal Block

■How to wire
1) Remove wire's insulation.
7 mm
2) Insert wire into the terminal block until it reaches the back of the block and fasten the screw in a
clockwise. (Fastening torque: 0.22 to 0.25N・m (2.3 to 2.5 kgf・cm))
■Notes for wiring
Take care not to break wire.
・When removing wire's insulation, take care not to scratch core wire.
・Do not twist the wires to connection.
・Do not solder wire to connect them. Soldering may break due to vibration.
・After wiring, do not make stress to the cable.
・On the structure of the terminal, if the wire tightens counterclockwise, it has connection problem.
Once remove the wire and check the terminal and fasten again.
Clockwise
■Applicable cable (strand wire)
Size
AWG28 to 16
■Applicable rod terminal
Manufacture
Phoenix Contact Co.
Counterclockwise
Cross-sectional area
2
0.08 to 1.25mm
Cross-sectional
Size
area
2
0.25mm
AWG #24
2
0.34mm
AWG #22
2
0.50mm
AWG #20
2
0.75mm
AWG #18
2
1.00mm
AWG #18
24
Model No.
With insulation
Without insulation
sleeve
AI 0,25-6 BU
AI 0,34-6 TQ
AI 0,5-6WH
AI 0,75-6GY
-
ELC500 Control unit
sleeve
A 0,25-7
A 0,34-7
A 0,5-6
A 0,75-6
A 1-6

Advertisement