(d)
Alarm mask time
(e)
Use the data of the previous
period
for
estimation.
(f)
Control demand value
(g)
Limit control demand value
(h)
Target demand value
(i)
Switch moving average time Select use the function, that it switches period 1st half and
(j)
Moving average time
st
1
half
(k)
Moving average time
nd
2
half
(l)
Switching time from 1
nd
2
half
* Set each value as the followings.
Target demand value ≧ Limit control demand value ≧ Control demand value
If it doesn't meet this condition, error message will be appeared.
Set alarm mask time.
<Initial> 0 min
<Set range> 0 to 10
Select use the function, it calculates estimated demand
demand
using the incline of power in the previous period, or not.
<Initial> without check = not available
Set control demand value
<Initial> 0 kW
<Set range> 0 to 999999999999999
Set limit control demand value
<Initial>0 kW
<Set range> 0 to 999999999999999 kW
Set target demand value
<Initial>0 kW
<Set range>0~999999999999999 kW
2nd half for calculate demand value increasing rate to
estimate dimmed, or not
<Initial> Yes
Set moving average time for 1
<Initial> 5 sec.
<Set range> 5 / 10 / 15 / 20 / 25 / 30 / 35 / 40 / 45 / 50
Set moving average time for 2
<Initial> 5 sec.
<Set range> 5 / 10 / 15 / 20 / 25 / 30 / 35 / 40 / 45 / 50
st
to
Set time to switch moving average time.
<Initial> 10 min.
<Set range> 10 to 20
113
ELC500 Control unit
st
half.
nd
half.