Cabling; Cabling Of Power Supply Unit - Panasonic ELC500 User Manual

Table of Contents

Advertisement

3.2

Cabling

3.2.1

Cabling of Power Supply Unit

■Wiring of power supply unit
Be sure to wire correctly according to the terminal arrangement and wiring diagrams.
After completing wiring, be sure to attach the terminal cover for safety reasons.
■Power supply voltage
Check that the connected power supply voltage is in the range of the allowable power supply.
Rated input
Model No.
AFP7PSA1
AFP7PSA2
Note
- To add voltage or frequency out of specification range or to use wire that is not allowable
cause damage to power supply.
- Do not connect AC power supply 100-240V to alarm output terminals.
■Power supply cable
In order to reduce the voltage drop, use electric wire of 2 mm
■Applicable wire and fastening torque
Terminal
Power supply terminals
Grounding terminals
Alarm output terminals
■Applicable crimping terminals
M3 terminal screws are used for terminals. Use the below crimping terminal for wiring.
3.2mmφ
Allowable
voltage
voltage
100 to
85 to 264VAC
240VAC
Applicable wire
AWG14 (2.0mm
AWG22 to 14 (0.3 to 2.0mm
Rated
frequency
50/60Hz
2
(AWG 14).
2
)
2
)
3.2mm
20
ELC500 Control unit
Rated output
Rated output
capacity
current
24W
43W
Fastening torque
0.5 to 0.6N・m
1A
1.8A