Standard Pause; Pause Hold - ProMinent DULCOMETER D1CA Operating Instructions Manual

Adjustment and operation, measured variable chlorite
Hide thumbs Also See for DULCOMETER D1CA:
Table of Contents

Advertisement

Complete Operating Menu / Description

Standard Pause

If the pause-switch is off, the DULCOMETER
pause-switch is off or for a set time-delay t
establishes the P-proportion in the background.
With PID-control (Identity code characteristics "control characteristic" = 2): the I-proportion is stored when
the pause is switched off (I-proportion then usually only present if Ti > 0 has been selected in the "Control
setting?" setting menu).
Exception: the standard signal outputs mA for the measured value or correction value are not affected by
the pause.
After pause is activated the operating outputs remain at "0" for the length of the time-delay t
delay t
must be set up in such a way that, in this time e.g. sample water (process-specific current
d
concentration) flows to the sensor.
With PID-control (Identity code characteristics "control characteristic" = 2): The control variable output
resulting from the pause and the expiry of the time-delay t
P-component and (if Ti is set > 0) with the stored I-component.

Pause Hold

If the pause-switch is off, the DULCOMETER
as long as the pause-switch is off or for a set time-delay t
is off, the D1C establishes the P-proportion in the background.
With PID-control (Identity code characteristics "control characteristic" = 2):
Even the mA standard signal outputs for measured value or correction value are frozen.
After pause is activated the operating outputs remain frozen for the length of the time delay t
delay t
must be set up in such a way that, in this time e.g. sample water (process-specific current
d
concentration) flows to the sensor.
With PID-control (Identity code characteristics "control characteristic" = 2): The control variable output
resulting from the pause and the expiry of the time-delay t
P-proportionand (if Ti is set > 0) with the newly established I-proportion.
24
®
D1C sets the operating outputs to "0" for as long as the
(if t
is set to > 0 min). Whilst the pause-switch is off, the D1C
d
d
®
D1C freezes the operating output at the most recent value for
(if t
d
d
is reconciled jointly with the current
d
is set to > 0 min). Whilst the pause-switch
is reconciled jointly with the current
d
. The time-
d
. The time
d