Restricted Operating Menu / Overview - ProMinent DULCOMETER D1CA Operating Instructions Manual

Adjustment and operation, measured variable chlorite
Hide thumbs Also See for DULCOMETER D1CA:
Table of Contents

Advertisement

7

Restricted Operating Menu / Overview

The restricted operating menu permits simple operation of the most important parameters. The following
overview shows the settings which can be selected:
ppm
0.55
mea. val 0.55 ppm
feedfwd:
70 %
ctrlout:
59 %
w:
0.40 ppm
calibration Clt
zero p.:
0.00 mA
slope
6.50 mA/ppm
limits
setting ?
Only with control
control
setting ?
Setting in
complete
operating
menu
general setting
information
8
Permanent display 1
Permanent display 2
only with control
(w = setpoint)
calibration Clt
DPD-value:
1.55 ppm
limit 2
upper
5.00 ppm
limit 1
lower
1.00 ppm
control
regulated value
positive chlorite
negative De-Clt
control
normal
current regulat.
value:
30 %
or
control
with dead zone
current regulat.
value:
30 %
or
control
manual
current regulat.
value:
30 %
ident-code: D1CA
DxIxxxxxxxxxx
software version
D1C-B1 FW-4.90
Positive values of setting variable: chlorite
Negative values of setting variable: De-Clt
calibration Clt
zero p.:
0.00 mA
slope
6.50 mA/ppm
For normal control
setpoint
0.50 ppm
Control with dead zone
setpoint 2 upper
0.50 ppm
setpoint 1 lower
0.40 ppm
For manual control
manual dosing
15 %
regulated range
alarm relay
active
(chlorite destruction)
Number and scope
of setting menus
is dependent
on the device.
Access to setting
menus can be blocked
with access code.
Proportional control
ctrl parameter
xp =
10 %
PID Control
ctrl parameter
xp =
10 %
Ti =
off
Td =
off
access c.:
5000
operating menu:
=
english
=
reduced
D1C2-Clt-010-GB

Advertisement