Zero Point - ProMinent DULCOMETER D1CA Operating Instructions Manual

Adjustment and operation, measured variable chlorite
Hide thumbs Also See for DULCOMETER D1CA:
Table of Contents

Advertisement

Complete Operating Menu / Description
Standard signal input
lower signal limit
Allocated measured
value
lower
upper
Checkout time

Zero point

Access to all setting menus can be blocked with an access code !
zero point
setting ?
Zero point setting
CLT 1-mA-0.5 ppm
CLT 1-mA-2 ppm
Pumps
Access to all setting menus can be blocked with an access code !
Only with pumps for control
pumps
setting ?
Max. stroke/minute of
pumps 1 and 2
Possible values
Initial value
Increment
4 mA
0 mA
4 mA
0 ppm
0.01 ppm
0 ppm
0.001 ppm
2.0 ppm
0.01 ppm
2.0 ppm
0.001 ppm
off
zero point
4.20 mA
value take over?
Possible values
Initial value
Increment
4.80 mA
0.01 mA
4.20 mA
control
pump 1 chlorit
pump 2 De-Clt
Possible values
Initial value
Increment
180
Lower value
-0.20 ppm
-0.05 ppm
-0.20 ppm
-0.05 ppm
1 s
1 s
Lower value
3.80 mA
dosing pump max.
pump 1:
pump 2:
pulse/minute
Lower value
1
1
Upper value
2.20 ppm
for CLT1-mA-2 ppm
0.550 ppm
for CLT1-mA-0.5 ppm
2.20 ppm
for CLT1-mA-2 ppm
0.550 ppm
for CLT1-mA-0.5 ppm
9999 s
Constant measurement signal
results in message and alarm.
Function off = 0 s
Upper value
6.00 mA
5.00 mA
180
180
Upper value
500
off = 0 strokes/min
Remarks
D1C2-Clt-031-GB
Remarks
D1C2-Clt-022-GB
Remarks
15