Installation
Remount the AC drive cover and run the cable as
shown in picture.
NOTE: When planning the cable runs, remember
to keep the distance between the fieldbus cable
and the motor cable at a minimum of 30 cm. It is
recommended to route the option board cables
away from the power cables as shown in the pic-
ture.
9
The bus termination must be set for the first and the last device of the fieldbus
line. See picture below. See also step 7 on page 38. We recommend that the first
device on the bus and, thus, terminated was the Master device.
10
Termination
activated
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Vacon 100 Vacon 100 Vacon 100 Vacon 100
Fieldbus cable
Termination
= Bus termination
deactivated
vacon • 39
Fieldbus
cables
9202.emf
Vacon 100
Termination
activated with
jumper
3007.emf
6