Siemens SINAMICS G120C Compact Operating Instructions page 80

Low-voltage inverters built-in devices, frame sizes d...f
Hide thumbs Also See for SINAMICS G120C:
Table of Contents

Advertisement

Troubleshooting and additional information
5.1 List of alarms and faults
Number
Cause
F01659
Write task for parameter rejected Cause: The inverter should be reset to the factory setting. However, it is not
F01662
CU hardware fault
A01666
Static 1 signal at the F-DI for
safe acknowledgement
A01698
Commissioning mode active for
safety functions
A01699
Switch-off signal path test re-
quired
F03505
Analog input, wire break
A03520
Temperature sensor fault
A05000
Power Module overtemperature
A05001
A05002
A05004
A05006
F06310
Supply voltage (p0210) incor-
rectly parameterized
F07011
Motor overtemperature
A07012
I2t motor model overtemperature Check and if necessary reduce the motor load.
A07015
Motor temperature sensor alarm
F07016
Motor temperature sensor fault
F07086
Unit switchover: Parameter limit
F07088
violation
80
Remedy
permissible to reset the safety functions as the safety functions are currently
enabled.
Remedy with operator panel:
p0010 = 30
Parameter reset
p9761 = ...
Enter password for the safety functions.
p0970 = 5
Reset start safety parameter.
The inverter sets p0970 = 5 once it has reset the pa-
rameter.
Then reset the inverter to the factory setting again.
Switch off the inverter and switch on again, upgrade the firmware or contact
technical support.
Set F-DI to a logical 0 signal.
This message is withdrawn after the Safety commissioning has ended.
After the next time that the "STO" function is deselected, the message is
withdrawn and the monitoring time is reset
Check the connection to the signal source for interrupts.
Check the level of the signal supplied.
The input current measured by the analog input can be read out in r0752.
Check that the sensor is connected correctly.
Check the following:
- Is the ambient temperature within the defined limit values?
- Are the load conditions and duty cycle configured accordingly?
- Has the cooling failed?
Check the parameterized supply voltage and if required change (p0210).
Check the line voltage.
Reduce the motor load.
Check ambient temperature.
Check sensor's wiring and connection.
Check the motor's ambient temperature.
Check thermal time constant p0611.
Check overtemperature fault threshold p0605.
Check that the sensor is connected correctly.
Check the parameter assignment (p0601).
Make sure that the sensor is connected correctly.
Check the parameterization (p0601).
Check the adapted parameter values and if required correct.
Compact Operating Instructions, 11/2016, FW V4.7 SP6, A5E39339884B AA