Installing
3.2 Connecting
Branch circuit protection according to the UL standard
Use in North America requires protection devices that meet UL standards as detailed in the
following tables.
Table 3- 4
Protection device
Fuses of any manufacturer with faster tripping characteristic than class RK5, e.g.
class J, T, CC, G, or CF
SIEMENS circuit breaker
Type E combination motor controller (designation according to the UL standard), is
available as SIEMENS circuit breaker
In accordance with the following tables, you may operate the inverter on a branch circuit with
the specified short-circuit current rating provided the specified branch-circuit protection is
installed.
Table 3- 5
Frame
size
FSD
FSE
FSF
Maximum rated current of the fuse
1)
Short circuit current rating of the inverter
2)
Minimum envelope dimensions of a control cabinet approved according to UL in which the inverter
3)
is installed.
22
Permissible safety devices according to the UL standard
Permissible circuit protection with non-semiconductor fuses of Classes J, T, CC, G or CF
(JDDZ)
Rated power
Inverter article number
22 kW
6SL3210-1KE24-4...
30 kW
6SL3210-1KE26-0...
37 kW
6SL3210-1KE27-0...
45 kW
6SL3210-1KE28-4...
55 kW
6SL3210-1KE31-1...
75 kW
6SL3210-1KE31-4...
90 kW
6SL3210-1KE31-7...
110 kW
6SL3210-1KE32-1...
132 kW
6SL3210-1KE32-4...
Compact Operating Instructions, 11/2016, FW V4.7 SP6, A5E39339884B AA
I
SCCR
1)
2)
max
70 A
65 kA, 3 AC 480 V
90 A
65 kA, 3 AC 480 V
100 A
65 kA, 3 AC 480 V
125 A
65 kA, 3 AC 480 V
150 A
65 kA, 3 AC 480 V
200 A
65 kA, 3 AC 480 V
250 A
65 kA, 3 AC 480 V
300 A
65 kA, 3 AC 480 V
350 A
65 kA, 3 AC 480 V
SINAMICS G120C, FSD ... FSF inverters
UL category
JDDZ
DIVQ
NKJH
Control
cabinet
3)
≥ 36000 in³
≥ 36000 in³
≥ 36000 in³
≥ 36000 in³
≥ 36000 in³
≥ 36000 in³
≥ 36000 in³
≥ 36000 in³
≥ 36000 in³