No.
Description
p1300
Open-loop/closed-loop control operating mode
0
V/f control with linear characteristic
1
V/f control with linear characteristic and
FCC
2
V/f control with parabolic characteristic
3
V/f control with parameterizable characteris-
tic
4
V/f control with linear characteristic and
ECO
5
V/f control for drive requiring a precise fre-
quency (e.g. textiles)
6
V/f control for drive requiring a precise fre-
quency and FCC
7
V/f control for parabolic characteristic and
ECO
19
V/f control with independent voltage setpoint
20
Speed control (without encoder)
p1302
V/f control configuration
p1310
Starting current (voltage boost) permanent
[100 % ≙ p0305]
p1311
Starting current (voltage boost) acceleration [%]
p1312
Starting current (voltage boost) when starting [%]
r1315
Voltage boost, total [100 % ≙ p2001]
SINAMICS G120C, FSD ... FSF inverters
Compact Operating Instructions, 11/2016, FW V4.7 SP6, A5E39339884B AA
4.2 Commissioning with BOP-2 operator panel
No.
Description
p1320
U/f control programmable frequency f [Hz] and
voltage U [V] characteristic
...
p1327
p1330
CI: V/f control independent voltage setpoint
[100 % ≙ p2001]
p1331
Voltage limiting [V]
p1333
U/f control FCC starting frequency [Hz]
p1334
V/f control slip compensation starting frequency
[Hz]
p1335
Slip compensation, scaling [100 % ≙ r0330]
p1336
Slip compensation limit value [100 % ≙ r0330]
r1337
CO: Actual slip compensation [100 ≙ 100%]
p1338
V/f mode resonance damping gain
p1340
I
frequency controller proportional gain
max
r1343
CO: I_max controller frequency output
[100 % ≙ p2000]
p1349
U/f mode resonance damping maximum frequen-
cy [Hz]
p1351
CO: Motor holding brake starting frequency
[100 ≙ 100%]
p1352
CI: Motor holding brake starting frequency
[100 ≙ 100%]