Installing
3.2 Connecting
Frame
Rated power
size
FSF
75 kW
90 kW
110 kW
132 kW
Maximum rated current of the circuit-breaker
1)
Short circuit current rating of the inverter
2)
Minimum envelope dimensions of a control cabinet approved according to UL in which the inverter is installed.
3)
65 kA, 480 VAC with rated current < 35 A
4)
24
Inverter article num-
ber
Article number
6SL3210-1KE31-4... NFGB, FXD6-A, FD6-A,
JD6-A, JXD6-A
HFGB, LFGB, HFD6,
HFXD6, HJD6-A,
HJXD6-A
HHFD6, HHFXD6, CFD6,
HHJD6, HHJXD6,
CJD6-A
6SL3210-1KE31-7... NFGB, FXD6-A, FD6-A,
JD6-A, JXD6-A
HFGB, LFGB, HFD6,
HFXD6, HJD6-A,
HJXD6-A
HHFD6, HHFXD6, CFD6,
HHJD6, HHJXD6,
CJD6-A
6SL3210-1KE32-1... NJGA, JD6-A, JXD6-A,
LD6-A, LXD6-A
HJGA, LJGA, HJD6-A,
HJXD6-A, HLD6-A,
HLXD6-A, HHLD6,
HHLXD6
HHJD6, HHJXD6,
CJD6-A, CLD6-A
6SL3210-1KE32-4... NJGA, JD6-A, JXD6-A,
LD6-A, LXD6-A
HJGA, LJGA, HJD6-A,
HJXD6-A, HLD6-A,
HLXD6-A, HHLD6,
HHLXD6
HHJD6, HHJXD6,
CJD6-A, CLD6-A
Circuit breaker
I
max 1)
200 A 35 kA, 480 VAC
200 A 65 kA, 480 VAC
200 A 100 kA, 480 V AC
250 A 35 kA, 480 V AC
250 A 65 kA, 480 VAC
250 A 100 kA, 480 V AC
300 A 35 kA, 480 VAC
300 A 65 kA, 480 VAC
300 A 100 kA, 480 V AC
350 A 35 kA, 480 VAC
350 A 65 kA, 480 VAC
350 A 100 kA, 480 V AC
Compact Operating Instructions, 11/2016, FW V4.7 SP6, A5E39339884B AA
SCCR
2)
SINAMICS G120C, FSD ... FSF inverters
Control
cabinet
3)
≥ 36600 in³
≥ 36600 in³
≥ 36600 in³
≥ 36600 in³
≥ 36600 in³
≥ 36600 in³
≥ 36600 in³
≥ 36600 in³
≥ 36600 in³
≥ 36600 in³
≥ 36600 in³
≥ 36600 in³