Commissioning
4.2 Commissioning with BOP-2 operator panel
Procedure when using the BOP-2 operator panel
To start the motor data identification, proceed as follows:
Press the HAND/AUTO key.
The BOP-2 displays the symbol indicating manual operation.
Switch on the motor.
During motor data identification, "MOT-ID" flashes on the BOP-2.
If the inverter again outputs alarm A07991, then it waits for a new ON command to start the
rotating measurement.
If the inverter does not output alarm A07991, switch off the motor as described below, and
switch over the inverter control from HAND to AUTO.
Switch on the motor to start the rotating measurement.
During motor data identification, "MOT-ID" flashes on the BOP-2.
The motor data identification can take up to 2 minutes depending on the rated motor power.
Depending on the setting, after motor data identification has been completed, the inverter
switches off the motor - or it accelerates it to the setpoint.
If required, switch off the motor.
Switch the inverter control from HAND to AUTO.
You have completed the motor data identification.
50
Compact Operating Instructions, 11/2016, FW V4.7 SP6, A5E39339884B AA
SINAMICS G120C, FSD ... FSF inverters