Table 1: VAV Controller Model Features
Feature
VAV100/101
(Discontinued)
Ambient
32 to 122°F
Temperature
(0 to 50°C)
Rating
Analog Inputs
RTD temperature
elements (1000 ohm
nickel, platinum, or
silicon)
2k ohm setpoint
potentiometers
0 to 10 VDC or
0 to 2 VDC
transmitters
Binary Inputs
(4) Dry contacts
(1) Momentary push
button from zone
sensor for temporary
occupancy mode
BI 4 may be used as
an accumulator input
for frequencies less
than 100 Hz.
Analog
Outputs
0 to 10 VDC
@ 10 mA
Binary
Outputs
24 VAC Triacs
@ 0.5 amperes
N2 Bus
Not Isolated *
Zone Bus
Discrete connections
at controller
8-pin phone jack on
controller
6-pin phone jack at
zone sensor
Quick Connects
24 VAC Power
(Spade Lugs) *
Terminations
I/O
Quick Connects
(Spade Lugs)
Terminations
N2
Fixed Screw Terminal
Block *
Terminations
* VAV Controller model feature differences
VAV110/111
32 to 122°F
(0 to 50°C)
6
6
RTD temperature
elements (1000 ohm
nickel, platinum, or
silicon)
2k ohm setpoint
potentiometers
0 to 10 VDC or
0 to 2 VDC
transmitters
4
4
(4) Dry contacts
(1) Momentary push
button from zone
sensor for temporary
occupancy mode
BI 4 may be used as
an accumulator input
for frequencies less
than 100 Hz.
0/2
0/2
0 to 10 VDC
@ 10 mA
8/6
8/6
24 VAC Triacs
@ 0.5 amperes, or
0.8 amperes if total
power is limited
Isolated
Discrete connections
at controller
8-pin phone jack on
controller
6-pin phone jack at
zone sensor
LED Indication *
Removable Screw
Terminal Block
Quick Connects
(Spade Lugs)
Removable Screw
Terminal Block
VAV Controller—Variable Air Volume (VAV) Controller 7
VAV140/141
32 to 122°F
(0 to 50°C)
6
RTD temperature
elements (1000 ohm
nickel, platinum, or
silicon)
2k ohm setpoint
potentiometers
0 to 10 VDC or
0 to 2 VDC
transmitters
4
(4) Dry contacts
(1) Momentary push
button from zone
sensor for temporary
occupancy mode
BI 4 may be used as
an accumulator input
for frequencies less
than 100 Hz.
0/2
0 to 10 VDC
@ 10 mA
8/6
24 VAC Triacs
@ 0.5 amperes, or
0.8 amperes if total
power is limited
Isolated
Discrete connections
at controller
8-pin and 6-pin phone
jack on controller *
6-pin phone jack at
zone sensor
LED Indication *
Removable Screw
Terminal Block
Fixed Screw Terminal
Block *
Removable Screw
Terminal Block