Hardware Point
Assignment
Table
The following table shows the HVAC PRO for Windows hardware point
assignments and options for single duct configurations.
Table 17: Single Duct Point Assignments and Options
Point
Point
HVAC PRO for Windows
Type
Name
Configuration
Assignments and Defaults
AI 1
Zone Temperature
Analog
Unused
Inputs
AI 3
Unused
AI 4
Actuator Feedback on Pressure
Dependent
CFM on Pressure Independent None
Unused
AI 5
Proportional Series Fan CFM
Exhaust Box CFM
Unused
AI 6
Unused
Binary
BI 1
Unused
Inputs
BI 2
Unused
BI 3
Unused
BI 4
Unused
Momentary
BI 5
Unused
BI
Continued on next page . . .
HVAC PRO for Windows
Configuration Options
None
Rename
Warmer/Cooler Adjust Potentiometer
Cooling Setpoint Potentiometer
Heating Setpoint Potentiometer
Rename
None
Rename
None
None
Rename
Box Supply Temperature for
Standalone Warmup in Pressure
Dependent with Feedback and
Independent Path
Rename
Rename
Occupied
Rename
Standby
Rename
Shutdown Box Open
Rename
Shutdown Box Closed
Temporary Occupancy Mode
Boost Mode
VAV Controller—Variable Air Volume (VAV) Controller 53