Iec Ratings; Ul (Nec) Ratings - ABB ACQ580-31 Quick Installation Manual

Table of Contents

Advertisement

4 EN – US quick installation guide
YY:
17, 18, 19, ... for 2017, 2018, 2019,
WW:
01, 02, 03, ... for week 1, week 2, week 3,
For information on reforming the capacitors, see Converter module capacitor
reforming instructions (3BFE64059629 [English]), available on the Internet at
abb.com/drives/documents.
Data

IEC ratings

ACQ580-31-
ES
3-phase U
= 480 V
N
09A5-4
FI
12A7-4
018A-4
FR
026A-4
033A-4
FR
039A-4
046A-4
NL
062A-4
073A-4
PL
088A-4
106A4
145A-4
PT
169A-4
206A-4
RU
SV

UL (NEC) ratings

TR
ACQ580-31-
3-phase U
= 480 V
N
ZH
07A6-4
012A-4
014A-4
023A-4
027A-4
034A-4
044A-4
052A-4
065A-4
077A-4
096A-4
124A-4
156A-4
180A-4
Cu cable (AWG/kcmil)
14
14
14
10
8
8
6
4
2
1/0
2/0
3/0
250 MCM
300 MCM
Cu cable (AWG/kcmil)
14
14
14
10
8
8
6
4
2
2
1/0
2/0
4/0
250 MCM
...
...
UL fuse
JJS-15
JJS-20
JJS-25
JJS-35
JJS-40
JJS-50
JJS-60
JJS-80
JJS-90
JJS-110
JJS-150
JJS-200
JJS-225
JJS-300
UL fuse
JJS-15
JJS-20
JJS-25
JJS-35
JJS-40
JJS-50
JJS-60
JJS-80
JJS-90
JJS-110
JJS-150
JJS-200
JJS-225
JJS-300
Losses (W)
219
278
321
473
625
711
807
960
1223
1560
1678
2237
2796
3356
3AXD00000586715
Losses (W)
219
278
321
473
625
711
807
960
1223
1560
1678
2237
2796
3356
3AXD00000586715