DSC 3G2060 Installation Manual page 48

Internet/hspa alarm communicator
Table of Contents

Advertisement

EN50131-1 Installation Requirements
For EN50131-1 compliant installations, the following programming options shall be set as described.
Supervision Heartbeat (required for ATS4 and ATS5):
• [851][004] set to 0087h (135s heartbeat).
NOTE: The compatible receiver at ARC location shall have supervision window programmed for 1800s (ATS4) or 180s (ATS 5).
• [851][005] options 1,2 and 3 shall be enabled
• [851][005] option 8 shall be enabled
Test transmission (required for ATS3):
• [851] System test options [026-029] shall be enabled (FF) for the communication paths available.
• [851][124-125] and [224-225] shall be programmed with time of day for test transmission and 1440 minutes (24h) for test trans-
mission cycle.
Configuration of communication paths (all ATS classes):
• [300][001] select option 02 for auto routing (this will allow transmission of the events over all available communication paths in the
system).
• [380] enable option 5 (YES) for parallel transmission over all available communication paths (if redundant configuration is
desired).
• [382] enable option 5 (YES) this will enable the alternate communicator.
• [384] enable the desired back-up configuration (receiver 2 back-up for receiver 1 or receiver 3 back-up for receiver 1).
EN50131 Compliant Installations
1. The TL2603G-EU, 3G2060-EU, TL260 module is monitored by the control panel and it is programmed via the programming
menu (* 8, section [851] in the control panel. The interface is connected to the PC-Link bus as shown in the diagram included in
this manual.
2. The Ethernet port is protected against surge transients up to 2.5kV and both Ethernet port and GPRS/3G Cellular path are immune
to conducted and radiated RF fields with levels up to 10V/m as tested per EN50130-4 Standard.
3. The TL2603G-EU, 3G2060-EU, TL260 module conforms with radiated emissions levels for Class B equipment as per standards
EN61000-6-3/EN55022/CISPR22.
4. The TL2603G-EU, 3G2060-EU, TL260 module uses AES128 encryption and heartbeat supervision for both Ethernet and GPRS/
3G Cellular communication paths and it meets security levels S2 as per EN50136-2-1 (EN50131-1). It also uses authentication for
each message exchanged with the compatible receiver equipment at ARC and it meets level I2 for information security.
5. The TL2603G-EU module has two communication paths: Ethernet 10/100BaseT and GPRS/3G Cellular communication path that
can be used in a redundant (parallel) mode or back-up mode configuration based on selecting the appropriate option in the pro-
gramming section [851][005]. The 3G2060-EU module has only one communication path:GPRS/3G Cellular communication path
using 900/1800/2100MHz Public Cellular Network. The TL260 module has only one communication path: Ethernet 10/100BaseT
using Internet/Intranet network.
TL2603G-EU, 3G2060-EU, TL260 have been certified by Telefication in accordance with EN50131-1 requirements for Grade 2,
Class II and ATS Class 3,4,5.
© 2017 Tyco Security Products. All Rights Reserved.
The trademarks, logos, and service marks displayed on this document are registered in the United States [and / or other countries].
Any misuse of the trademarks is strictly prohibited and Tyco will aggressively enforce its intellectual property rights to the fullest
extent of the law, including pursuit of criminal prosecution wherever necessary. All trademarks not owned by Tyco are the property
of their respective owners, and are used with permission or allowed under applicable laws.
Product offerings and specifications are subject to change without notice. Actual products may vary from photos. Not all products
include all features. Availability varies by region; contact your sales representative.
www.dsc.com
29009176R003

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tl2603gTl260

Table of Contents