Appendix G-Factory Default Configuration V3.1X; 910 Series Htc - nvent 910 Series Installation, Operating And Maintenance Instructions

Table of Contents

Advertisement

APPENDIX G—FACTORY DEFAULT CONFIGURATION V3.1X

910 SERIES HTC

74 | nVent.com
BASIC MODE MENU
(All other parameters are set as shown in the Advanced Mode Sub-Menus)
Configuration Mode Menu
Parameter
Factory
Control Setpoint
68°F (20°C)
Lo TS 1
14°F (–10°C)
Lo Load
1.0A
Switch Control Mode
Deadband
Circuit Breaker
*n/a (30.0A)
Temperature Units
°F
Feature Mode
Basic
ADVANCED MODE MENUS
Configuration Mode Main Menu
Parameter
Factory
Control Setpoint
68°F (20°C)
Lo TS 1
14°F (–10°C)
Lo Load
1.0 A
Hi GFI
20 mA
GFI Trip
30 mA
Feature Mode
Advanced
TS Alarms Configuration Sub-Menu
Parameter
Factory
TS 1 Fail
Enable
Lo TS 1
Enable
Lo TS 1
14°F (–10°C)
Hi TS 1
Disable
Hi TS 1
*n/a
(212°F (100°C))
TS 2 Fail
Disable
Lo TS 2
Disable
Lo TS 2
*n/a
(14°F (–10°C))
Hi TS 2
Disable
Hi TS 2
*n/a
(212°F (100°C))
Lo TS Filter
0 min
Hi TS Filter
*n/a (0 min)
Latch TS Alarms
Yes
CTL TS Fail
Enable
User
User
User

Hide quick links: