4.3.3 "TS ALARMS CONFIG..." SUB-MENU
This sub-menu is used to set up alarms that relate to any of the temperature sensors.
Each alarm may be ENAbled or DISabled, and if the alarm is ENAbled,
an alarm setting may be entered.
CONTROL SETPOINT = 20°C
LO TS 1 = –10°C
LO LOAD = 1.0 A
HI GFI = 50 mA
GFI TRIP = 75 mA
TS ALARMS CONFIG...
OTHER ALARMS CONFIG...
POINT SETUP...
MISC SETUP...
COMMUNICATIONS SETUP...
---- END ----
Table 4.6 TS Alarms Configuration Sub-Menu
TS 1 FAIL
LO TS 1
LO TS 1
HI TS 1
HI TS 1
TS 2 FAIL
LO TS 2
LO TS 2
HI TS 2
HI TS 2
LO TS FILTERS
HI TS FILTERS
LATCH TS ALARMS
CTL TS FAIL
---- END ----
4.3.4 "OTHER ALARMS CONFIG..." SUB-MENU
This sub-menu allows the user to set up all alarms that do not directly relate to the temperature
sensors. These include all AC alarms (voltage, current. ground fault, etc.) as well as protection
settings such as power limiting, etc.
Each alarm may be ENAbled or DISabled. If the alarm is ENAbled, an alarm setting and filter
setting may be entered.
=
{ENA or DIS}
=
{ENA or DIS}
=
{–60 TO 570}°C
=
{ENA or DIS}
=
{–60 TO 570}°C
=
{ENA or DIS}
=
{ENA or DIS}
=
{–60 TO 570}°C
=
{ENA or DIS}
=
{–60 TO 570}°C
=
{0 to 999} MIN (only if LO TS 1 or 2 are enabled)
=
{0 to 999} MIN (only if HI TS 1 or 2 are enabled)
=
{YES or NO}
=
{ENA or DIS}
nVent.com | 21